Conduit Fill Chart (NEC Chapter 9)
The existing calculator applies NEC Chapter 9 fill percentages. Areas below are calculated from its stored internal diameters using A = πd²/4; they are not transcribed NEC Table 4 area values.
Coverage: EMT, RMC, PVC Schedule 40 and PVC Schedule 80: listed trade sizes 1/2–4 in. Areas rounded to three decimal places.
Use cable outside dimensions, not bare conductor area. Short-nipple exceptions require checking the applicable rule. Fill approval does not establish ampacity or pulling suitability.
Fill percentages
| Conductor count | % |
|---|---|
| 1 | 53 |
| 2 | 31 |
| > 2 | 40 |
EMT
| Trade size (in) | Internal diameter (in) | Total (in²) | 53% (in²) | 31% (in²) | 40% (in²) |
|---|---|---|---|---|---|
| 1 | 1.049 | 0.864 | 0.458 | 0.268 | 0.346 |
| 2 | 2.067 | 3.356 | 1.778 | 1.040 | 1.342 |
| 3 | 3.356 | 8.846 | 4.688 | 2.742 | 3.538 |
| 4 | 4.334 | 14.753 | 7.819 | 4.573 | 5.901 |
| 1/2 | 0.622 | 0.304 | 0.161 | 0.094 | 0.122 |
| 3/4 | 0.824 | 0.533 | 0.283 | 0.165 | 0.213 |
| 1-1/4 | 1.38 | 1.496 | 0.793 | 0.464 | 0.598 |
| 1-1/2 | 1.61 | 2.036 | 1.079 | 0.631 | 0.814 |
| 2-1/2 | 2.731 | 5.858 | 3.105 | 1.816 | 2.343 |
| 3-1/2 | 3.834 | 11.545 | 6.119 | 3.579 | 4.618 |
RMC
| Trade size (in) | Internal diameter (in) | Total (in²) | 53% (in²) | 31% (in²) | 40% (in²) |
|---|---|---|---|---|---|
| 1 | 1.063 | 0.887 | 0.470 | 0.275 | 0.355 |
| 2 | 2.083 | 3.408 | 1.806 | 1.056 | 1.363 |
| 3 | 3.09 | 7.499 | 3.975 | 2.325 | 3.000 |
| 4 | 4.05 | 12.882 | 6.828 | 3.994 | 5.153 |
| 1/2 | 0.632 | 0.314 | 0.166 | 0.097 | 0.125 |
| 3/4 | 0.836 | 0.549 | 0.291 | 0.170 | 0.220 |
| 1-1/4 | 1.394 | 1.526 | 0.809 | 0.473 | 0.610 |
| 1-1/2 | 1.624 | 2.071 | 1.098 | 0.642 | 0.829 |
| 2-1/2 | 2.489 | 4.866 | 2.579 | 1.508 | 1.946 |
| 3-1/2 | 3.57 | 10.010 | 5.305 | 3.103 | 4.004 |
PVC Schedule 40
| Trade size (in) | Internal diameter (in) | Total (in²) | 53% (in²) | 31% (in²) | 40% (in²) |
|---|---|---|---|---|---|
| 1 | 1.029 | 0.832 | 0.441 | 0.258 | 0.333 |
| 2 | 2.047 | 3.291 | 1.744 | 1.020 | 1.316 |
| 3 | 3.042 | 7.268 | 3.852 | 2.253 | 2.907 |
| 4 | 3.998 | 12.554 | 6.654 | 3.892 | 5.022 |
| 1/2 | 0.602 | 0.285 | 0.151 | 0.088 | 0.114 |
| 3/4 | 0.804 | 0.508 | 0.269 | 0.157 | 0.203 |
| 1-1/4 | 1.36 | 1.453 | 0.770 | 0.450 | 0.581 |
| 1-1/2 | 1.59 | 1.986 | 1.052 | 0.616 | 0.794 |
| 2-1/2 | 2.445 | 4.695 | 2.488 | 1.455 | 1.878 |
| 3-1/2 | 3.521 | 9.737 | 5.161 | 3.018 | 3.895 |
PVC Schedule 80
| Trade size (in) | Internal diameter (in) | Total (in²) | 53% (in²) | 31% (in²) | 40% (in²) |
|---|---|---|---|---|---|
| 1 | 0.957 | 0.719 | 0.381 | 0.223 | 0.288 |
| 2 | 1.939 | 2.953 | 1.565 | 0.915 | 1.181 |
| 3 | 2.9 | 6.605 | 3.501 | 2.048 | 2.642 |
| 4 | 3.826 | 11.497 | 6.093 | 3.564 | 4.599 |
| 1/2 | 0.546 | 0.234 | 0.124 | 0.073 | 0.094 |
| 3/4 | 0.742 | 0.432 | 0.229 | 0.134 | 0.173 |
| 1-1/4 | 1.278 | 1.283 | 0.680 | 0.398 | 0.513 |
| 1-1/2 | 1.5 | 1.767 | 0.937 | 0.548 | 0.707 |
| 2-1/2 | 2.323 | 4.238 | 2.246 | 1.314 | 1.695 |
| 3-1/2 | 3.364 | 8.888 | 4.711 | 2.755 | 3.555 |
How to use this chart
Choose the raceway and trade size, then the fill percentage for the conductor count. Compare the sum of occupied areas with available area.
Worked example
3/4 in EMT: π × 0.824²/4 ≈ 0.533 in² total; 40% ≈ 0.213 in² available.
Method & Sources
This is a reference chart; it does not run a calculator method.
Sources
- NFPA 70, National Electrical Code (NEC), Chapter 9 fill percentages; areas calculated from existing internal diametersEdition not stated on this page; clause and table identifiers are preserved verbatim.
Related calculators
FAQ
What does this chart cover?
EMT, RMC, PVC Schedule 40 and PVC Schedule 80: listed trade sizes 1/2–4 in. Areas rounded to three decimal places.
Where do the values come from?
The existing calculator applies NEC Chapter 9 fill percentages. Areas below are calculated from its stored internal diameters using A = πd²/4; they are not transcribed NEC Table 4 area values.
How do I read this chart?
Choose the raceway and trade size, then the fill percentage for the conductor count. Compare the sum of occupied areas with available area.
Can you show an example?
3/4 in EMT: π × 0.824²/4 ≈ 0.533 in² total; 40% ≈ 0.213 in² available.
What limits must I check?
Use cable outside dimensions, not bare conductor area. Short-nipple exceptions require checking the applicable rule. Fill approval does not establish ampacity or pulling suitability.