Voltage Drop Calculator
Estimate voltage drop by current, conductor length, material, cross-section, and phase system.
Open calculatorEngineering calculators for cable sizing, AC and DC voltage drop, derating, AWG conversion, PE conductors, and thermal withstand.
8 calculatorsEstimate voltage drop by current, conductor length, material, cross-section, and phase system.
Open calculatorFind a reference conductor size from load current, sizing factor, conductor material, and installation severity.
Open calculatorCheck DC voltage drop for 12 V, 24 V, 48 V, control, LED, battery, and PV accessory circuits using AWG conductor resistance.
Open calculatorFind the smallest AWG conductor that passes both reference ampacity and voltage-drop checks.
Open calculatorConvert conductor cross-sectional area between metric mm² and American Wire Gauge, with nearest and not-smaller standard-size references.
Open calculatorCombine ambient-temperature, grouping, installation, and soil factors to estimate corrected cable ampacity.
Open calculatorCalculate minimum protective-conductor cross-section using the IEC adiabatic equation and a user-selected material k value.
Open calculatorCheck cable short-circuit thermal withstand using conductor area, fault current, duration, and material k value.
Open calculatorCable and wire selection must satisfy current-carrying capacity, voltage drop, installation derating, terminal limits, and short-circuit thermal withstand. Conductor material and cross-sectional area alone do not complete the selection.
These tools separate conductor electrical performance from the physical routing and termination questions covered under Cable Management & Installation.
A conductor can pass ampacity but fail voltage drop on a long run, or pass normal operation but fail the adiabatic short-circuit check. Each condition should be calculated on the same load, route, material, and protection basis.
AWG and mm² are different nominal systems. A nearest conversion is useful for comparison, but final selection should use an available standard size that is not smaller than the required electrical area.
Estimate conductor size from load, phase, installation method, and allowable voltage drop.
Control voltage loss in battery, PV accessory, LED, control, and automotive-style circuits.
Compare conductor area with fault current and protective-device clearing time.
No. Ampacity is only one requirement. Voltage drop, fault withstand, installation method, ambient temperature, grouping, terminals, and mechanical minimums can require a larger conductor.
No. Outside diameter includes insulation, fillers, screens, armor, and sheath. Conductor cross-sectional area must come from the cable construction or datasheet.
Use nearest AWG for reference. For capacity selection, use a standard conductor whose verified area and ampacity meet or exceed the requirement.