Wire Ampacity Chart (NEC Table 310.16)
Copper to Aluminum Conductor Conversion Calculator
NEC Table 310.16 base values: 30 °C ambient and not more than three current-carrying conductors.
IAl ≥ ICuwhere:
- IAl
- Aluminum table ampacity[A]
- ICu
- Copper table ampacity[A]
Calculation basis
Find the smallest listed aluminum conductor with at least the copper ampacity in NEC Table 310.16 at 75 or 90 degrees Celsius.
NEC Table 310.16 base values: 30 °C ambient and not more than three current-carrying conductors.
Verified tables and sources
Values are transcribed from NEC Table 310.16 reproduced in Liberty Residential Service Standards 2025, printed page 74. A dash means no listed value.
| Size | Cu 75 °C / A | Cu 90 °C / A | Al 75 °C / A | Al 90 °C / A |
|---|---|---|---|---|
| 14 AWG | 20 | 25 | — | — |
| 12 AWG | 25 | 30 | 20 | 25 |
| 10 AWG | 35 | 40 | 30 | 35 |
| 8 AWG | 50 | 55 | 40 | 45 |
| 6 AWG | 65 | 75 | 50 | 55 |
| 4 AWG | 85 | 95 | 65 | 75 |
| 3 AWG | 100 | 115 | 75 | 85 |
| 2 AWG | 115 | 130 | 90 | 100 |
| 1 AWG | 130 | 145 | 100 | 115 |
| 1/0 AWG | 150 | 170 | 120 | 135 |
| 2/0 AWG | 175 | 195 | 135 | 150 |
| 3/0 AWG | 200 | 225 | 155 | 175 |
| 4/0 AWG | 230 | 260 | 180 | 205 |
| 250 kcmil | 255 | 290 | 205 | 230 |
| 300 kcmil | 285 | 320 | 230 | 260 |
| 350 kcmil | 310 | 350 | 250 | 280 |
| 400 kcmil | 335 | 380 | 270 | 305 |
| 500 kcmil | 380 | 430 | 310 | 350 |
| 600 kcmil | 420 | 475 | 340 | 385 |
| 700 kcmil | 460 | 520 | 375 | 425 |
| 750 kcmil | 475 | 535 | 385 | 435 |
| 800 kcmil | 490 | 555 | 395 | 445 |
| 900 kcmil | 520 | 585 | 425 | 480 |
| 1000 kcmil | 545 | 615 | 445 | 500 |
| 1250 kcmil | 590 | 665 | 485 | 545 |
| 1500 kcmil | 625 | 705 | 520 | 585 |
| 1750 kcmil | 650 | 735 | 545 | 615 |
| 2000 kcmil | 665 | 750 | 560 | 630 |
Worked examples
3 AWG copper is 100 A; 1 AWG aluminum is the smallest listed size reaching 100 A.
4/0 AWG copper and 300 kcmil aluminum each have a 230 A table ampacity.
Method & Sources
Method
Formula used
IAl ≥ ICu
Input basis
NEC Table 310.16 base values: 30 °C ambient and not more than three current-carrying conductors.
- Copper conductor size
- Ampacity temperature column
- IAl — Aluminum table ampacity [A]
- ICu — Copper table ampacity [A]
Units
A
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- NEC Table 310.16 base values: 30 °C ambient and not more than three current-carrying conductors.
- The 90 °C column does not authorize 90 °C terminations. NEC 110.14, AL/CU compatibility, derating, voltage drop and small-conductor protection still govern.
Sources
- NFPA 70, National Electrical Code (NEC), 2023 edition, Table 310.16Edition: as cited on this page. Clause and table identifiers are preserved verbatim.
- NFPA 70, National Electrical Code (NEC), 2023 edition, 110.14Edition: as cited on this page. Clause and table identifiers are preserved verbatim.
- Liberty Residential Service Standards 2025, printed page 74Reproduction of NEC Table 310.16 ampacity values used by the calculator.
Application limits
The 90 °C column does not authorize 90 °C terminations. NEC 110.14, AL/CU compatibility, derating, voltage drop and small-conductor protection still govern.
No. This comparison uses thermal ampacity only; check voltage drop separately.
The calculator reports no listed size. It does not invent a larger conductor or design parallel runs.
Assumptions
- NEC Table 310.16 base values: 30 °C ambient and not more than three current-carrying conductors.
Important Warnings
- The 90 °C column does not authorize 90 °C terminations. NEC 110.14, AL/CU compatibility, derating, voltage drop and small-conductor protection still govern.