Wire resistance equation
Resistance increases with resistivity and conductor length and decreases with cross-sectional area.
RT = (ρ20 × L / A) × [1 + α × (T − 20)]R1000ft = RT / Lft × 1000Rkm = RT / Lkmwhere:
- RT
- Conductor resistance at temperature T[Ω]
- ρ20
- Material resistivity at 20 °C[Ω·mm²/m]
- L
- One-conductor length[m]
- A
- Nominal conductor area[mm²]
- α
- Material temperature coefficient[1/°C]
- T
- Conductor temperature[°C]
The result is one conductor's resistance; a complete two-wire circuit normally includes the return path.
How to calculate wire resistance
Multiply the material resistivity at 20 °C by the one-conductor length, divide by the conductor area, then apply the selected temperature coefficient.
- Select copper or aluminum.
- Enter an AWG size or metric area.
- Enter the length of one conductor.
- Enter the conductor temperature and review both normalized resistance outputs.
Worked 12 AWG copper example
For 12 AWG copper, 100 ft, and 75 °C, the shared voltage-drop model uses an AWG nominal area of about 3.31 mm² and copper ρ20 = 0.0175 Ω·mm²/m. At 20 °C the one-conductor resistance is about 0.161 Ω; at 75 °C the correction produces about 0.196 Ω.
R75 = 0.161 × [1 + 0.00393 × 55] ≈ 0.196 Ω
R ≈ 1.96 Ω/1000 ft ≈ 6.43 Ω/km
Method & Sources
Method
Formula used
RT = (ρ20 × L / A) × [1 + α × (T − 20)]R1000ft = RT / Lft × 1000Rkm = RT / Lkm
Input basis
Resistance increases with resistivity and conductor length and decreases with cross-sectional area.
- Conductor material
- Conductor size input
- AWG conductor size
- Conductor cross-sectional area [mm²]
- One-conductor length [ft]
- Conductor temperature [°C]
- RT — Conductor resistance at temperature T [Ω]
- ρ20 — Material resistivity at 20 °C [Ω·mm²/m]
- L — One-conductor length [m]
- A — Nominal conductor area [mm²]
- α — Material temperature coefficient [1/°C]
- T — Conductor temperature [°C]
Units
mm² · ft · m · °C · °F · Ω · Ω·mm²/m · 1/°C
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- The result is for one conductor, not the outgoing-and-return loop.
- Copper and aluminum resistivity and AWG nominal area use the same basis as the voltage-drop calculator.
- The temperature correction is linear around 20 °C using the selected material coefficient.
- Stranding, compaction, temperature rating, and manufacturer construction can differ from the nominal round-conductor model.
- Use the conductor manufacturer or the adopted wiring table when a verified design resistance is required.
- The result is one conductor's resistance; a complete two-wire circuit normally includes the return path.
Sources
- Estimation basis: published page formula, assumptions, and warningsEstimation basisNo separate public standard is cited; the published equation and stated input scope form a planning or screening basis.
Why 0.193 Ω is a different basis
A value near 0.193 Ω is associated with a table-specific 75 °C conductor resistance. It is not the result of the main voltage-drop calculator's ρ/area model. This page keeps one shared model so the two tools cannot silently disagree.
One conductor versus a complete circuit
The reported resistance belongs to one length of conductor. A two-wire voltage-drop calculation normally includes the outgoing and return conductor, so its conductor contribution is approximately twice this value.
Temperature and design limits
The linear temperature correction is an estimate. Final cable design also depends on insulation temperature rating, terminals, installation method, grouping, frequency, skin effect, reactance, and the adopted wiring standard.
Assumptions
- The result is for one conductor, not the outgoing-and-return loop.
- Copper and aluminum resistivity and AWG nominal area use the same basis as the voltage-drop calculator.
- The temperature correction is linear around 20 °C using the selected material coefficient.
Important Warnings
- Stranding, compaction, temperature rating, and manufacturer construction can differ from the nominal round-conductor model.
- Use the conductor manufacturer or the adopted wiring table when a verified design resistance is required.