Cable, Wire & Voltage Drop Tools

Wire Ampacity Chart (NEC Table 310.16)

NEC Table 310.16 values already used by the copper-to-aluminum calculator: 30 °C ambient, not more than three current-carrying conductors. Only the available 75 °C and 90 °C columns are reproduced.

Coverage: Copper: 14 AWG–2000 kcmil; aluminum: 12 AWG–2000 kcmil. No 60 °C column. A dash means unavailable, not zero ampacity.

Apply NEC 110.14 termination limits, ambient and grouping corrections, and small-conductor protection rules. A 25 A table value does not authorize a 25 A breaker on 12 AWG. Cable Size uses a separate preliminary sizing model; this chart does not convert that model into NEC design approval.

NEC 310.16

Conductor sizeCopper 75 °C (A)Copper 90 °C (A)Aluminum 75 °C (A)Aluminum 90 °C (A)
14 AWG2025——
12 AWG25302025
10 AWG35403035
8 AWG50554045
6 AWG65755055
4 AWG85956575
3 AWG1001157585
2 AWG11513090100
1 AWG130145100115
1/0 AWG150170120135
2/0 AWG175195135150
3/0 AWG200225155175
4/0 AWG230260180205
250 kcmil255290205230
300 kcmil285320230260
350 kcmil310350250280
400 kcmil335380270305
500 kcmil380430310350
600 kcmil420475340385
700 kcmil460520375425
750 kcmil475535385435
800 kcmil490555395445
900 kcmil520585425480
1000 kcmil545615445500
1250 kcmil590665485545
1500 kcmil625705520585
1750 kcmil650735545615
2000 kcmil665750560630

How to use this chart

Choose material, conductor size and the permitted temperature column, then apply the installation corrections.

Worked example

12 AWG copper at 75 °C: 25 A. 1/0 aluminum at 75 °C: 120 A. 4/0 copper at 90 °C: 260 A.

Method & Sources

This is a reference chart; it does not run a calculator method.

Sources

  • NFPA 70, National Electrical Code (NEC), Table 310.16 (existing calculator data)Edition not stated on this page; clause and table identifiers are preserved verbatim.
  • NFPA 70, National Electrical Code (NEC), 110.14 termination limitsEdition not stated on this page; clause and table identifiers are preserved verbatim.
  • Liberty Residential Service Standards 2025, printed page 74Reproduction of NEC Table 310.16 ampacity values used by the calculator.

Related calculators

FAQ

What does this chart cover?

Copper: 14 AWG–2000 kcmil; aluminum: 12 AWG–2000 kcmil. No 60 °C column. A dash means unavailable, not zero ampacity.

Where do the values come from?

NEC Table 310.16 values already used by the copper-to-aluminum calculator: 30 °C ambient, not more than three current-carrying conductors. Only the available 75 °C and 90 °C columns are reproduced.

How do I read this chart?

Choose material, conductor size and the permitted temperature column, then apply the installation corrections.

Can you show an example?

12 AWG copper at 75 °C: 25 A. 1/0 aluminum at 75 °C: 120 A. 4/0 copper at 90 °C: 260 A.

What limits must I check?

Apply NEC 110.14 termination limits, ambient and grouping corrections, and small-conductor protection rules. A 25 A table value does not authorize a 25 A breaker on 12 AWG. Cable Size uses a separate preliminary sizing model; this chart does not convert that model into NEC design approval.