Wire Ampacity Chart (NEC Table 310.16)
NEC Table 310.16 values already used by the copper-to-aluminum calculator: 30 °C ambient, not more than three current-carrying conductors. Only the available 75 °C and 90 °C columns are reproduced.
Coverage: Copper: 14 AWG–2000 kcmil; aluminum: 12 AWG–2000 kcmil. No 60 °C column. A dash means unavailable, not zero ampacity.
Apply NEC 110.14 termination limits, ambient and grouping corrections, and small-conductor protection rules. A 25 A table value does not authorize a 25 A breaker on 12 AWG. Cable Size uses a separate preliminary sizing model; this chart does not convert that model into NEC design approval.
NEC 310.16
| Conductor size | Copper 75 °C (A) | Copper 90 °C (A) | Aluminum 75 °C (A) | Aluminum 90 °C (A) |
|---|---|---|---|---|
| 14 AWG | 20 | 25 | — | — |
| 12 AWG | 25 | 30 | 20 | 25 |
| 10 AWG | 35 | 40 | 30 | 35 |
| 8 AWG | 50 | 55 | 40 | 45 |
| 6 AWG | 65 | 75 | 50 | 55 |
| 4 AWG | 85 | 95 | 65 | 75 |
| 3 AWG | 100 | 115 | 75 | 85 |
| 2 AWG | 115 | 130 | 90 | 100 |
| 1 AWG | 130 | 145 | 100 | 115 |
| 1/0 AWG | 150 | 170 | 120 | 135 |
| 2/0 AWG | 175 | 195 | 135 | 150 |
| 3/0 AWG | 200 | 225 | 155 | 175 |
| 4/0 AWG | 230 | 260 | 180 | 205 |
| 250 kcmil | 255 | 290 | 205 | 230 |
| 300 kcmil | 285 | 320 | 230 | 260 |
| 350 kcmil | 310 | 350 | 250 | 280 |
| 400 kcmil | 335 | 380 | 270 | 305 |
| 500 kcmil | 380 | 430 | 310 | 350 |
| 600 kcmil | 420 | 475 | 340 | 385 |
| 700 kcmil | 460 | 520 | 375 | 425 |
| 750 kcmil | 475 | 535 | 385 | 435 |
| 800 kcmil | 490 | 555 | 395 | 445 |
| 900 kcmil | 520 | 585 | 425 | 480 |
| 1000 kcmil | 545 | 615 | 445 | 500 |
| 1250 kcmil | 590 | 665 | 485 | 545 |
| 1500 kcmil | 625 | 705 | 520 | 585 |
| 1750 kcmil | 650 | 735 | 545 | 615 |
| 2000 kcmil | 665 | 750 | 560 | 630 |
How to use this chart
Choose material, conductor size and the permitted temperature column, then apply the installation corrections.
Worked example
12 AWG copper at 75 °C: 25 A. 1/0 aluminum at 75 °C: 120 A. 4/0 copper at 90 °C: 260 A.
Method & Sources
This is a reference chart; it does not run a calculator method.
Sources
- NFPA 70, National Electrical Code (NEC), Table 310.16 (existing calculator data)Edition not stated on this page; clause and table identifiers are preserved verbatim.
- NFPA 70, National Electrical Code (NEC), 110.14 termination limitsEdition not stated on this page; clause and table identifiers are preserved verbatim.
- Liberty Residential Service Standards 2025, printed page 74Reproduction of NEC Table 310.16 ampacity values used by the calculator.
Related calculators
FAQ
What does this chart cover?
Copper: 14 AWG–2000 kcmil; aluminum: 12 AWG–2000 kcmil. No 60 °C column. A dash means unavailable, not zero ampacity.
Where do the values come from?
NEC Table 310.16 values already used by the copper-to-aluminum calculator: 30 °C ambient, not more than three current-carrying conductors. Only the available 75 °C and 90 °C columns are reproduced.
How do I read this chart?
Choose material, conductor size and the permitted temperature column, then apply the installation corrections.
Can you show an example?
12 AWG copper at 75 °C: 25 A. 1/0 aluminum at 75 °C: 120 A. 4/0 copper at 90 °C: 260 A.
What limits must I check?
Apply NEC 110.14 termination limits, ambient and grouping corrections, and small-conductor protection rules. A 25 A table value does not authorize a 25 A breaker on 12 AWG. Cable Size uses a separate preliminary sizing model; this chart does not convert that model into NEC design approval.