Box Fill Volume Chart (NEC 314.16)
Existing NEC 314.16(B) conductor allowances and the calculator’s NEC 314.16(A) metal-box subset. Volume allowances are not a count of physical wires alone.
Coverage: 18–6 AWG: seven allowances. Twelve device/square metal boxes, 7.5–42.0 in³. Other box types are not included.
Check the marked volume and actual device fit. NEC 2020/2023 grounding allowances differ from 2017: up to four entering grounds share one allowance, with a quarter allowance for each additional ground.
NEC 314.16(B)
| AWG | in³ |
|---|---|
| 18 | 1.50 |
| 16 | 1.75 |
| 14 | 2.00 |
| 12 | 2.25 |
| 10 | 2.50 |
| 8 | 3.00 |
| 6 | 5.00 |
NEC 314.16(A)
| Box dimensions and type | in³ |
|---|---|
| 3 × 2 × 1½ in — device | 7.5 |
| 3 × 2 × 2 in — device | 10.0 |
| 3 × 2 × 2¼ in — device | 10.5 |
| 3 × 2 × 2½ in — device | 12.5 |
| 3 × 2 × 2¾ in — device | 14.0 |
| 3 × 2 × 3½ in — device | 18.0 |
| 4 × 1¼ in — square | 18.0 |
| 4 × 1½ in — square | 21.0 |
| 4¹¹⁄₁₆ × 1¼ in — square | 25.5 |
| 4¹¹⁄₁₆ × 1½ in — square | 29.5 |
| 4 × 2⅛ in — square | 30.3 |
| 4¹¹⁄₁₆ × 2⅛ in — square | 42.0 |
How to use this chart
Multiply each counted allowance by its conductor-size volume, add device/clamp/grounding allowances under the adopted edition, and compare with marked box volume.
Worked example
12 AWG requires 2.25 in³ per allowance. Eight allowances require 18.0 in³; a 4 in square × 1½ in deep box provides 21.0 in³ and passes this volume check.
Method & Sources
This is a reference chart; it does not run a calculator method.
Sources
- NFPA 70, National Electrical Code (NEC), 2020 / 2023 editions, 314.16(A)/(B)Edition: as cited on this page. Clause and table identifiers are preserved verbatim.
- Southwire: NEC 314.16(A)/(B) tablesPublished table reproduction linked from this page.
- Leviton: 2020 NEC grounding revisionEstimation basisPublished revision note linked from this page.
- NFPA: 314.16 revision recordOfficial code-development record linked from this page; confirm the locally adopted edition.
Related calculators
FAQ
What does this chart cover?
18–6 AWG: seven allowances. Twelve device/square metal boxes, 7.5–42.0 in³. Other box types are not included.
Where do the values come from?
Existing NEC 314.16(B) conductor allowances and the calculator’s NEC 314.16(A) metal-box subset. Volume allowances are not a count of physical wires alone.
How do I read this chart?
Multiply each counted allowance by its conductor-size volume, add device/clamp/grounding allowances under the adopted edition, and compare with marked box volume.
Can you show an example?
12 AWG requires 2.25 in³ per allowance. Eight allowances require 18.0 in³; a 4 in square × 1½ in deep box provides 21.0 in³ and passes this volume check.
What limits must I check?
Check the marked volume and actual device fit. NEC 2020/2023 grounding allowances differ from 2017: up to four entering grounds share one allowance, with a quarter allowance for each additional ground.