Box Fill Calculator

Calculate required electrical box volume from conductor sizes, device yokes, internal clamps and grounding conductors using NEC 314.16.

NEC 314.16

Box Fill Volume Chart (NEC 314.16)

Box fill equation

Add the conductor, device, clamp and grounding volumes, then compare with the selected box capacity.

V = Σ(n × a) + 2yaᵧ + caₘ + gaɢ
Fill % = 100 × V / Vbox

where:

n
Count of conductors of each AWG size
a
Volume allowance for that AWG size[in³]
y
Number of ordinary device yokes
aᵧ
Allowance for the largest conductor connected to a yoke[in³]
c
One if internal clamps are present, otherwise zero
aₘ
Allowance for the largest conductor in the box[in³]
g
Grounding allowance multiplier for the selected NEC edition
aɢ
Allowance for the largest entering grounding conductor[in³]
Vbox
Selected box capacity[in³]

Conductor allowances — NEC 314.16(B)

Use the allowance for each wire size, not a single average size. The conductor counts exclude grounds, which have their own input.

AWGin³
181.50
161.75
142.00
122.25
102.50
83.00
65.00

Standard metal boxes — NEC 314.16(A)

This verified subset includes device and square metal boxes only. Use the marked capacity for other boxes. A volume match does not establish device fit.

Standard metal boxin³
3 × 2 × 1½ in — device7.5
3 × 2 × 2 in — device10.0
3 × 2 × 2¼ in — device10.5
3 × 2 × 2½ in — device12.5
3 × 2 × 2¾ in — device14.0
3 × 2 × 3½ in — device18.0
4 × 1¼ in — square18.0
4 × 1½ in — square21.0
4¹¹⁄₁₆ × 1¼ in — square25.5
4¹¹⁄₁₆ × 1½ in — square29.5
4 × 2⅛ in — square30.3
4¹¹⁄₁₆ × 2⅛ in — square42.0

Worked example: two 12/2 cables

Four 12 AWG insulated conductors, one receptacle yoke, internal clamps and two entering grounds require (4 + 2 + 1 + 1) × 2.25 = 18.0 in³. A 4 × 1½ in square box has 21.0 in³: 85.71% utilization, PASS.

The smallest listed device box by volume is 3 × 2 × 3½ in, 18.0 in³, exactly 100%. The 4 × 1¼ in square box also provides 18.0 in³; verify device depth and cover suitability.

Method & Sources

Method

Formula used

  • V = Σ(n × a) + 2yaᵧ + caₘ + gaɢ
  • Fill % = 100 × V / Vbox

Input basis

Add the conductor, device, clamp and grounding volumes, then compare with the selected box capacity.

  • NEC edition
  • 18 AWG
  • 16 AWG
  • 14 AWG
  • 12 AWG
  • 10 AWG
  • 8 AWG
  • 6 AWG
  • Device yokes
  • Largest conductor connected to yokes
  • Internal cable clamps
  • Grounding conductors entering the box
  • Largest grounding conductor
  • Standard metal box
  • n — Count of conductors of each AWG size
  • a — Volume allowance for that AWG size [in³]
  • y — Number of ordinary device yokes
  • aᵧ — Allowance for the largest conductor connected to a yoke [in³]
  • c — One if internal clamps are present, otherwise zero
  • aₘ — Allowance for the largest conductor in the box [in³]
  • g — Grounding allowance multiplier for the selected NEC edition
  • aɢ — Allowance for the largest entering grounding conductor [in³]
  • Vbox — Selected box capacity [in³]

Units

in³

Display and rounding

No separate display or rounding rule is stated on this page.

Scope and limits

  • Enter insulated conductor counts separately from grounding conductors. Count each entering or passing conductor once; omit pigtails entirely within the box.
  • Ordinary single-gang devices only. Long unbroken loops, support fittings, barriers, isolated grounds and oversized devices require a separate calculation.
  • PASS means volume only. Confirm device depth, box listing, marked volume and the locally adopted NEC edition.
  • The smallest recommendation is limited to the listed boxes. A suitable cover and device mounting arrangement are still required.

Sources

Worked example: overfilled box

Six 12 AWG insulated conductors, one receptacle yoke, internal clamps and three entering grounds require (6 + 2 + 1 + 1) × 2.25 = 22.5 in³. The 21.0 in³ square box is 107.14% full: FAIL. The smallest listed larger box is 4¹¹⁄₁₆ × 1¼ in square, 25.5 in³.

Edition, scope and sources

The 2020/2023 grounding rule adds one quarter allowance for each entering ground beyond four. The 2017 option applies one allowance to the ordinary grounding group. This tool does not cover isolated grounding sets or special exceptions.

Tables are checked against Southwire, Boxes & Covers, printed page 11-220. The grounding revision is documented by Leviton and NFPA. Confirm the locally adopted edition before installation.

Assumptions

  • Enter insulated conductor counts separately from grounding conductors. Count each entering or passing conductor once; omit pigtails entirely within the box.
  • Ordinary single-gang devices only. Long unbroken loops, support fittings, barriers, isolated grounds and oversized devices require a separate calculation.

Important Warnings

  • PASS means volume only. Confirm device depth, box listing, marked volume and the locally adopted NEC edition.
  • The smallest recommendation is limited to the listed boxes. A suitable cover and device mounting arrangement are still required.

FAQ

How much volume does a 12 AWG conductor require?

NEC Table 314.16(B) assigns 2.25 in³ per 12 AWG conductor allowance.

Does a receptacle count as one allowance?

No. An ordinary single-gang receptacle yoke counts as two allowances based on the largest conductor connected to it.

How are internal clamps counted?

One or more internal cable clamps together add one allowance based on the largest conductor in the box. External clamp mechanisms add none.

Do all grounding conductors count as one?

Under NEC 2020/2023, up to four entering grounding conductors count as one allowance; each additional conductor adds one quarter. NEC 2017 uses one allowance for the ordinary grounding group.

Does a volume PASS approve the installation?

No. The result compares volume only; device fit, mounting, conductor handling and local requirements still need verification.