Box Fill Volume Chart (NEC 314.16)
Box fill equation
Add the conductor, device, clamp and grounding volumes, then compare with the selected box capacity.
V = Σ(n × a) + 2yaᵧ + caₘ + gaɢFill % = 100 × V / Vboxwhere:
- n
- Count of conductors of each AWG size
- a
- Volume allowance for that AWG size[in³]
- y
- Number of ordinary device yokes
- aᵧ
- Allowance for the largest conductor connected to a yoke[in³]
- c
- One if internal clamps are present, otherwise zero
- aₘ
- Allowance for the largest conductor in the box[in³]
- g
- Grounding allowance multiplier for the selected NEC edition
- aɢ
- Allowance for the largest entering grounding conductor[in³]
- Vbox
- Selected box capacity[in³]
Conductor allowances — NEC 314.16(B)
Use the allowance for each wire size, not a single average size. The conductor counts exclude grounds, which have their own input.
| AWG | in³ |
|---|---|
| 18 | 1.50 |
| 16 | 1.75 |
| 14 | 2.00 |
| 12 | 2.25 |
| 10 | 2.50 |
| 8 | 3.00 |
| 6 | 5.00 |
Standard metal boxes — NEC 314.16(A)
This verified subset includes device and square metal boxes only. Use the marked capacity for other boxes. A volume match does not establish device fit.
| Standard metal box | in³ |
|---|---|
| 3 × 2 × 1½ in — device | 7.5 |
| 3 × 2 × 2 in — device | 10.0 |
| 3 × 2 × 2¼ in — device | 10.5 |
| 3 × 2 × 2½ in — device | 12.5 |
| 3 × 2 × 2¾ in — device | 14.0 |
| 3 × 2 × 3½ in — device | 18.0 |
| 4 × 1¼ in — square | 18.0 |
| 4 × 1½ in — square | 21.0 |
| 4¹¹⁄₁₆ × 1¼ in — square | 25.5 |
| 4¹¹⁄₁₆ × 1½ in — square | 29.5 |
| 4 × 2⅛ in — square | 30.3 |
| 4¹¹⁄₁₆ × 2⅛ in — square | 42.0 |
Worked example: two 12/2 cables
Four 12 AWG insulated conductors, one receptacle yoke, internal clamps and two entering grounds require (4 + 2 + 1 + 1) × 2.25 = 18.0 in³. A 4 × 1½ in square box has 21.0 in³: 85.71% utilization, PASS.
The smallest listed device box by volume is 3 × 2 × 3½ in, 18.0 in³, exactly 100%. The 4 × 1¼ in square box also provides 18.0 in³; verify device depth and cover suitability.
Method & Sources
Method
Formula used
V = Σ(n × a) + 2yaᵧ + caₘ + gaɢFill % = 100 × V / Vbox
Input basis
Add the conductor, device, clamp and grounding volumes, then compare with the selected box capacity.
- NEC edition
- 18 AWG
- 16 AWG
- 14 AWG
- 12 AWG
- 10 AWG
- 8 AWG
- 6 AWG
- Device yokes
- Largest conductor connected to yokes
- Internal cable clamps
- Grounding conductors entering the box
- Largest grounding conductor
- Standard metal box
- n — Count of conductors of each AWG size
- a — Volume allowance for that AWG size [in³]
- y — Number of ordinary device yokes
- aᵧ — Allowance for the largest conductor connected to a yoke [in³]
- c — One if internal clamps are present, otherwise zero
- aₘ — Allowance for the largest conductor in the box [in³]
- g — Grounding allowance multiplier for the selected NEC edition
- aɢ — Allowance for the largest entering grounding conductor [in³]
- Vbox — Selected box capacity [in³]
Units
in³
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- Enter insulated conductor counts separately from grounding conductors. Count each entering or passing conductor once; omit pigtails entirely within the box.
- Ordinary single-gang devices only. Long unbroken loops, support fittings, barriers, isolated grounds and oversized devices require a separate calculation.
- PASS means volume only. Confirm device depth, box listing, marked volume and the locally adopted NEC edition.
- The smallest recommendation is limited to the listed boxes. A suitable cover and device mounting arrangement are still required.
Sources
- NFPA 70, National Electrical Code (NEC), 2017 / 2020 / 2023 editions, 314.16Edition: as cited on this page. Clause and table identifiers are preserved verbatim.
- Southwire: NEC 314.16(A)/(B) tablesPublished table reproduction linked from this page.
- Leviton: 2020 NEC grounding revisionEstimation basisPublished revision note linked from this page.
- NFPA: 314.16 revision recordOfficial code-development record linked from this page; confirm the locally adopted edition.
Worked example: overfilled box
Six 12 AWG insulated conductors, one receptacle yoke, internal clamps and three entering grounds require (6 + 2 + 1 + 1) × 2.25 = 22.5 in³. The 21.0 in³ square box is 107.14% full: FAIL. The smallest listed larger box is 4¹¹⁄₁₆ × 1¼ in square, 25.5 in³.
Edition, scope and sources
The 2020/2023 grounding rule adds one quarter allowance for each entering ground beyond four. The 2017 option applies one allowance to the ordinary grounding group. This tool does not cover isolated grounding sets or special exceptions.
Tables are checked against Southwire, Boxes & Covers, printed page 11-220. The grounding revision is documented by Leviton and NFPA. Confirm the locally adopted edition before installation.
Southwire: NEC tables 314.16(A) and (B)Leviton: 2020 NEC grounding revisionNFPA: 314.16 revision record
Assumptions
- Enter insulated conductor counts separately from grounding conductors. Count each entering or passing conductor once; omit pigtails entirely within the box.
- Ordinary single-gang devices only. Long unbroken loops, support fittings, barriers, isolated grounds and oversized devices require a separate calculation.
Important Warnings
- PASS means volume only. Confirm device depth, box listing, marked volume and the locally adopted NEC edition.
- The smallest recommendation is limited to the listed boxes. A suitable cover and device mounting arrangement are still required.