Pull box sizing equations
Apply the straight-pull or row rule to each axis, then check the separation of each connected entry pair.
Lₛ = 8DₛLᵣ = 6D + Σ(other sizes)S = 6dL = max(Lₛ, Lᵣ)where:
- Lₛ
- Minimum straight-pull length[in]
- Dₛ
- Largest straight-pull raceway trade size on the axis[in]
- Lᵣ
- Minimum distance from a row to the opposite wall[in]
- D
- Largest raceway trade size in the row[in]
- Σ(other sizes)
- Sum of all remaining entries in the same wall and row[in]
- S
- Minimum clear separation between connected openings[in]
- d
- Larger trade size of the connected pair[in]
- L
- Governing inside distance when both rules apply[in]
Choose the correct NEC box calculation
Use NEC 314.28 for pull-space dimensions with insulated conductors 4 AWG and larger. This inch-based tool checks a single axis or row and one connected pair at a time; it does not calculate cubic-inch box fill.
Use the Box Fill Calculator for NEC 314.16 volume allowances. Check conduit fill separately before choosing the raceway trade size.
NEC 314.28 calculation rules
The multipliers below are dimension rules, not a table of commercially available boxes. Measure usable inside distances; a nominal enclosure size alone does not establish clearance.
| Arrangement | Minimum distance |
|---|---|
| Straight pull | 8 × Dₛ |
| Angle pull / U pull / splices | 6 × D + Σ(other sizes) |
| Connected entries | 6 × d |
| Mixed pulls on one axis | max(Lₛ, Lᵣ) |
Worked example: angle pull passes
A row contains one 3 in and two 2 in raceways. Required distance to the opposite wall is 6 × 3 + 2 + 2 = 22 in (558.8 mm). An available inside distance of 24 in passes the row check.
For a connected 3 in / 2 in pair, required edge-to-edge separation is 6 × 3 = 18 in. An actual gap of 18 in passes. Both entered checks PASS; other rows, pairs and depth still require verification.
Method & Sources
Method
Formula used
Lₛ = 8DₛLᵣ = 6D + Σ(other sizes)S = 6dL = max(Lₛ, Lᵣ)
Input basis
Apply the straight-pull or row rule to each axis, then check the separation of each connected entry pair.
- Pull arrangement
- Largest straight-pull raceway on this axis
- Row group A: trade size
- Row group A: raceway count
- Row group B: trade size
- Row group B: raceway count
- Row group C: trade size
- Row group C: raceway count
- Available inside distance to opposite wall [in]
- Connected entry A: trade size
- Connected entry B: trade size
- Clear distance between connected entries [in]
- Lₛ — Minimum straight-pull length [in]
- Dₛ — Largest straight-pull raceway trade size on the axis [in]
- Lᵣ — Minimum distance from a row to the opposite wall [in]
- D — Largest raceway trade size in the row [in]
- Σ(other sizes) — Sum of all remaining entries in the same wall and row [in]
- S — Minimum clear separation between connected openings [in]
- d — Larger trade size of the connected pair [in]
- L — Governing inside distance when both rules apply [in]
Units
in
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- Use inch trade sizes, not actual outside diameters. The millimetre result is a physical conversion, not a metric-designator calculation.
- Enter all raceways in one row on one wall, grouped into up to three distinct sizes. Repeat for every row, wall, axis and connected entry pair; the largest required distance governs.
- PASS applies only to the entered distances, not approval of a complete box. Depth, opening placement, fittings, covers, terminals and manufacturer instructions require separate checks.
- The removable-cover exception and specially listed smaller boxes are not calculated. For cables, determine the equivalent minimum raceway trade size first.
Sources
- NFPA 70, National Electrical Code (NEC), 2017 / 2020 / 2023 editions, 314.28Edition not stated on this page; clause and table identifiers are preserved verbatim.
- NFPA 314.28 revision recordOfficial code-development record linked from this page; not a substitute for the adopted code.
- Mike Holt: NEC 314.28 explanationEstimation basisPublished explanation linked from this page; not a substitute for the adopted code.
Worked example: insufficient wall distance
Keep the same 3, 2 and 2 in row and 18 in pair clearance, but reduce the inside distance to 20 in. The row still requires 22 in, so the result is FAIL with a 2 in shortfall.
For comparison, a straight pull with a 3 in largest raceway requires 8 × 3 = 24 in. If straight and angle pulls share that axis, use the larger requirement: max(24, 22) = 24 in.
Multiple rows, depth and exceptions
Evaluate rows separately rather than adding all walls together. On each axis retain the largest result, and verify each connected pair against its own six-times clearance. Three size groups are supported per row; layouts with more distinct sizes need a separate calculation.
The tool does not apply the removable-cover exception in Table 312.6(A), special listings, terminal bending spaces or high-voltage box rules. It is scoped to ordinary low-voltage installations at 1000 V or below using the 2017/2020/2023 rules; confirm the locally adopted edition.
For a cable entry, first find the minimum raceway trade size that would contain its conductors. Millimetre outputs here convert inch distances at 25.4 mm/in; they do not substitute NEC metric designators.
Sources and product selection
Rules are based on NEC 314.28(A)(1) and (A)(2), cross-checked with Mike Holt’s published explanation and the NFPA revision record. The NFPA document is a code-development record, not a substitute for the adopted code.
Select a listed enclosure only after checking all required inside distances, entry layout, environment and manufacturer instructions. No unverified standard box sizes are recommended.
Mike Holt: NEC 314.28 explanationNFPA: 314.28 revision record
Assumptions
- Use inch trade sizes, not actual outside diameters. The millimetre result is a physical conversion, not a metric-designator calculation.
- Enter all raceways in one row on one wall, grouped into up to three distinct sizes. Repeat for every row, wall, axis and connected entry pair; the largest required distance governs.
Important Warnings
- PASS applies only to the entered distances, not approval of a complete box. Depth, opening placement, fittings, covers, terminals and manufacturer instructions require separate checks.
- The removable-cover exception and specially listed smaller boxes are not calculated. For cables, determine the equivalent minimum raceway trade size first.