Select language

Choose the language for the tools.

Circuit Protection & Grounding

Circuit Breaker Size Calculator

Estimate a standard MCB or MCCB current rating from load power, voltage, phase, power factor, and sizing factor.

Circuit breaker sizing equation

This calculator estimates the load current, applies a sizing factor, and rounds up to the next common breaker rating.

DC load current
I = PV
Single-phase AC load current
I = P VPF
Three-phase AC load current
I = P 3VPF
Minimum breaker rating
Ib,min = IF
Standard rating selection
Ib = next standard size ≥ Ib,min

where:

I
Calculated load current[A]
P
Load power converted to watts[W]
V
System voltage[V]
PF
Power factor for AC loads
F
Sizing factor, entered as a percentage and converted to a multiplier
Ib,min
Minimum calculated breaker current rating[A]
Ib
Recommended standard breaker current rating[A]

Current rating is only one part of breaker selection. Trip curve, short-circuit breaking capacity, cable protection, selectivity, and product standard must also be verified.

How to calculate circuit breaker size

Breaker current sizing begins by converting load power to current for DC, single-phase AC, or three-phase AC. The calculator multiplies load current by the selected sizing factor and rounds upward to the next listed standard current rating.

  1. Select the electrical system type.
  2. Enter load power, voltage, and AC power factor.
  3. Apply the project sizing or continuous-load factor.
  4. Round up to a standard breaker current rating.
  5. Verify cable protection, trip characteristic, breaking capacity, and selectivity.

Circuit breaker sizing example

A balanced three-phase 15 kW load at 400 V and 0.85 power factor draws about 25.5 A. Applying a 125% sizing factor gives a minimum rating of about 31.8 A, so the calculator selects the next listed size of 32 A.

I = 15,000 / (√3 × 400 × 0.85) = 25.5 A

Ib,min = 25.5 × 1.25 = 31.8 A → 32 A

Input or resultValue
Load15 kW three-phase
Voltage400 V
Power factor0.85
Sizing factor125%
Recommended current rating32 A

Breaker current rating is not breaking capacity

The ampere rating describes normal-current and overload behavior. Breaking capacity describes the prospective short-circuit current the device can interrupt at a stated voltage and standard. Both must be adequate, and they cannot be inferred from each other.

Breaker characteristicSelection question
Rated current or settingCan it carry the load and protect the conductor?
Trip curve or protection settingsWill it coordinate with starting current and downstream devices?
Breaking capacityCan it interrupt the available fault current?
Poles and voltageDoes it match the circuit and isolation requirements?

MCB vs. MCCB selection after sizing

Current alone does not decide whether a miniature circuit breaker or molded-case circuit breaker is appropriate. Required breaking capacity, adjustable protection, frame size, coordination, mounting, standard, and application determine the product family.

Coordinate breaker and cable sizing

The selected breaker must protect the downstream conductor while carrying the design load. Confirm the relationship between design current, breaker rating or setting, and corrected cable ampacity, then check available fault current.

Assumptions

  • Standard rating list is used for preliminary selection
  • Trip curve, breaking capacity, coordination, and local code are not selected automatically

Important Warnings

  • Do not select a breaker from current alone. Verify cable ampacity, short-circuit current, trip curve, and equipment standard.
  • Continuous-load rules differ by market and application.

FAQ

Why does the calculator round up?

Protective devices are sold in standard current ratings. The tool rounds the calculated minimum to the next common rating.

Does this choose MCB or MCCB?

No. It estimates current rating only. The product family depends on breaking capacity, setting range, application, and standard.