Circuit Breaker Size Chart: NEC Wire & OCPD Guide
Copper ampacities from the existing NEC Table 310.16 data, paired with NEC 240.4(D) small-conductor caps, NEC 240.4(B) next-higher rating screening, and NEC 2023 Table 240.6(A) standard ratings. Conditions: 30 °C ambient and not more than three current-carrying conductors.
Coverage: Copper 14 AWG–4/0 AWG; 60 °C and 75 °C ampacities; standard ratings 10–300 A. The 60 °C column is limited to the existing AWG calculator range. Unlisted larger kcmil rows are not included.
NEC 240.4(B) does not override 240.4(D) small-conductor limits and is not available for the exceptions or multioutlet receptacle circuits described in 240.4(B). Motor circuits, continuous loads, tap conductors, fixture wire and other special applications use their own rules. Verify the adopted edition, equipment marking, voltage, interrupting rating, cable ampacity and manufacturer data. Sources: NEC 310.16, NEC 240.4(D), NEC 240.4(B), and Eaton’s reproduction of NEC 2023 Table 240.6(A).
NEC 310.16 / 240.4(D) / 240.4(B) / 240.6(A)
| Conductor size | Copper 60 °C (A) | Copper 75 °C (A) | Maximum breaker (A) |
|---|---|---|---|
| 14 AWG | 15 | 20 | 15 |
| 12 AWG | 20 | 25 | 20 |
| 10 AWG | 30 | 35 | 30 |
| 8 AWG | 40 | 50 | 50 |
| 6 AWG | 55 | 65 | 70 |
| 4 AWG | 70 | 85 | 90 |
| 3 AWG | 85 | 100 | 100 |
| 2 AWG | 95 | 115 | 125 |
| 1 AWG | 110 | 130 | 150 |
| 1/0 AWG | 125 | 150 | 150 |
| 2/0 AWG | 145 | 175 | 175 |
| 3/0 AWG | 165 | 200 | 200 |
| 4/0 AWG | 195 | 230 | 250 |
NEC 2023 Table 240.6(A)
| Standard rating (A) | Standard rating (A) | Standard rating (A) | Standard rating (A) |
|---|---|---|---|
| 10 | 15 | 20 | 25 |
| 30 | 35 | 40 | 45 |
| 50 | 60 | 70 | 80 |
| 90 | 100 | 110 | 125 |
| 150 | 175 | 200 | 225 |
| 250 | 300 | — | — |
How to use this chart
Find the copper size, apply installation corrections and NEC 110.14 terminal limits, then read the maximum breaker. For 14, 12 and 10 AWG, the 240.4(D) cap governs; larger rows show a 240.4(B) next-higher-rating screen only.
Worked example
12 AWG copper: 25 A at 75 °C, but NEC 240.4(D) caps the breaker at 20 A. 10 AWG: 30 A. 6 AWG: 65 A → next 240.6(A) rating 70 A. 4/0 AWG: 230 A → 250 A.
Method & Sources
This is a reference chart; it does not run a calculator method.
Sources
- NFPA 70, National Electrical Code (NEC), Table 310.16 (existing calculator data)Edition not stated on this page; clause and table identifiers are preserved verbatim.
- NFPA 70, National Electrical Code (NEC), 2023 edition, 240.4(B)/(D) and Table 240.6(A)Edition: as cited on this page. Clause and table identifiers are preserved verbatim.
- Eaton: NEC 2023 Table 240.6(A) reproductionPublished standard-rating reproduction used by the existing chart data.
Related calculators
FAQ
What does this chart cover?
Copper 14 AWG–4/0 AWG; 60 °C and 75 °C ampacities; standard ratings 10–300 A. The 60 °C column is limited to the existing AWG calculator range. Unlisted larger kcmil rows are not included.
Where do the values come from?
Copper ampacities from the existing NEC Table 310.16 data, paired with NEC 240.4(D) small-conductor caps, NEC 240.4(B) next-higher rating screening, and NEC 2023 Table 240.6(A) standard ratings. Conditions: 30 °C ambient and not more than three current-carrying conductors.
How do I read this chart?
Find the copper size, apply installation corrections and NEC 110.14 terminal limits, then read the maximum breaker. For 14, 12 and 10 AWG, the 240.4(D) cap governs; larger rows show a 240.4(B) next-higher-rating screen only.
Can you show an example?
12 AWG copper: 25 A at 75 °C, but NEC 240.4(D) caps the breaker at 20 A. 10 AWG: 30 A. 6 AWG: 65 A → next 240.6(A) rating 70 A. 4/0 AWG: 230 A → 250 A.
What limits must I check?
NEC 240.4(B) does not override 240.4(D) small-conductor limits and is not available for the exceptions or multioutlet receptacle circuits described in 240.4(B). Motor circuits, continuous loads, tap conductors, fixture wire and other special applications use their own rules. Verify the adopted edition, equipment marking, voltage, interrupting rating, cable ampacity and manufacturer data. Sources: NEC 310.16, NEC 240.4(D), NEC 240.4(B), and Eaton’s reproduction of NEC 2023 Table 240.6(A).