Motor FLA Chart (NEC 430.248 & 430.250)

Existing general-motor current tables from NFPA 70, 2023 edition: NEC 430.250 three-phase and 430.248 single-phase. Values are amperes.

Coverage: Three-phase: listed 1/2–200 HP rows at 208/230/460/575 V. Single-phase: listed 1/6–10 HP rows at 115/230 V. Unlisted combinations are not interpolated.

Table full-load current supports conductor and short-circuit/ground-fault protection sizing under the applicable NEC rules. Motor overload protection generally uses nameplate current and applicable motor conditions, not these table currents alone.

Three-phase — NEC 430.250

HP208 V (A)230 V (A)460 V (A)575 V (A)
1/22.42.21.10.9
3/43.53.21.61.3
14.64.22.11.7
1.56.6632.4
27.56.83.42.7
310.69.64.83.9
516.715.27.66.1
7.524.222119
1030.8281411
1546.2422117
2059.4542722
2574.8683427
3088804032
401141045241
501431306552
601691547762
752111929677
10027324812499
125343312156125
150396360180144
200528480240192

Single-phase — NEC 430.248

HP115 V (A)230 V (A)
1/64.42.2
1/45.82.9
1/37.23.6
1/29.84.9
3/413.86.9
1168
1.52010
22412
33417
55628
1010050

How to use this chart

Select phase first, then the HP row and voltage column. Do not substitute formula current for a required table lookup.

Worked example

Three-phase: 10 HP at 460 V = 14 A; 25 HP at 460 V = 34 A. Single-phase: 1 HP at 230 V = 8 A.

Method & Sources

This is a reference chart; it does not run a calculator method.

Sources

Related calculators

FAQ

What does this chart cover?

Three-phase: listed 1/2–200 HP rows at 208/230/460/575 V. Single-phase: listed 1/6–10 HP rows at 115/230 V. Unlisted combinations are not interpolated.

Where do the values come from?

Existing general-motor current tables from NFPA 70, 2023 edition: NEC 430.250 three-phase and 430.248 single-phase. Values are amperes.

How do I read this chart?

Select phase first, then the HP row and voltage column. Do not substitute formula current for a required table lookup.

Can you show an example?

Three-phase: 10 HP at 460 V = 14 A; 25 HP at 460 V = 34 A. Single-phase: 1 HP at 230 V = 8 A.

What limits must I check?

Table full-load current supports conductor and short-circuit/ground-fault protection sizing under the applicable NEC rules. Motor overload protection generally uses nameplate current and applicable motor conditions, not these table currents alone.