Power factor and correction equations
Real power, reactive power, and apparent power form a right-angled power triangle. Power factor is the ratio of real power to apparent power. Correction supplies part of the reactive power locally to reduce source current.
PF = P / S = cos φφ1 = cos⁻¹(PF1), φ2 = cos⁻¹(PF2)I = P / (√3 × V × PF)where:
- P
- Active power of the load[kW]
- Q
- Reactive power of the load[kvar]
- S
- Apparent power supplied to the load[kVA]
- PF
- Power factor, equal to real power divided by apparent power
- Qc
- Capacitive reactive power required[kvar]
- PF1
- Existing power factor
- PF2
- Target power factor
- φ
- Phase angle corresponding to the power factor
- I
- AC line current[A]
The power-triangle result describes one operating point. A real correction bank needs practical steps, switching control, harmonic assessment, voltage margin, discharge, and thermal design.
How to calculate power factor
Choose the pair of values available from a meter, nameplate, or load study. The calculator completes the power triangle and reports power factor, phase angle, real power, reactive power, apparent power, and line current.
- Select single-phase or three-phase AC.
- Choose the known-value combination.
- Enter two power quantities or the meter readings.
- Review PF and phase angle.
- Use correction mode only when a capacitor-bank estimate is required.
Real, reactive, and apparent power
Real power P in kW performs useful work. Reactive power Q in kvar supports alternating electric and magnetic fields. Apparent power S in kVA is the RMS voltage-current loading seen by cables, transformers, and switchgear. These quantities satisfy S² = P² + Q² for the sinusoidal displacement-power model.
PF = P / S = cos φ
S² = P² + Q²
Power factor calculation example
A load using 100 kW at 125 kVA has a power factor of 0.80. The corresponding reactive power is 75 kvar and the phase angle is approximately 36.87°. On a balanced 400 V three-phase supply, 125 kVA corresponds to approximately 180 A of line current.
PF = 100 kW / 125 kVA = 0.80
Q = √(125² − 100²) = 75 kvar
I = 125,000 / (√3 × 400) ≈ 180 A
Single-phase and three-phase line current
For single-phase AC, apparent power is voltage multiplied by current. For balanced three-phase AC, use line-to-line voltage and the √3 factor. Power factor is required when calculating current from real power, but not when apparent power in kVA is already known.
Single-phase: I = P / (V × PF)
Three-phase: I = P / (√3 × VLL × PF)
Three-phase from kVA: I = S × 1000 / (√3 × VLL)
How to calculate capacitor kvar
Enter active power, existing power factor, target power factor, voltage, and phase. The calculator converts each power factor to its phase angle and subtracts the target reactive-power requirement from the existing requirement.
- Measure or obtain real kW and power factor.
- Choose a justified target.
- Calculate required kvar.
- Compare current before and after correction.
- Design practical switching steps and harmonic protection.
Power factor correction example
For a 100 kW load improving from 0.75 to 0.95 power factor, the mathematical compensation is approximately 55 kvar. The final bank may use several switched stages so correction follows the changing load.
Qc = 100 × [tan(cos⁻¹ 0.75) - tan(cos⁻¹ 0.95)]
Qc ≈ 55 kvar
Why line current decreases
With useful kW held constant, improved power factor lowers kVA. Lower apparent power reduces line current, conductor loss, voltage drop, and transformer loading, but it does not reduce the mechanical output power required by the load.
Displacement power factor and true power factor
The simple relation PF = cos φ applies directly to sinusoidal voltage and current and describes displacement power factor. Nonlinear loads introduce distortion, so a meter may report a lower true power factor even when displacement power factor is high. Use measured kW and true RMS kVA when harmonics are significant.
Harmonics and capacitor-bank design
VFDs, UPS systems, welders, rectifiers, and nonlinear loads can create harmonic resonance and excess capacitor current. Measure harmonic conditions and evaluate detuned reactors, filters, capacitor voltage margin, capacitor-duty contactors, discharge resistors, ventilation, and automatic controller settings.
Assumptions
- Balanced steady-state AC load
- Power-triangle analysis represents a sinusoidal displacement-power model
- Active power remains constant after correction
- Capacitor steps and harmonic resonance are not modeled
Important Warnings
- Do not raise the target above the utility or project requirement; overcorrection can create leading power factor and overvoltage.
- Sites with VFDs, UPS systems, rectifiers, or significant harmonics require harmonic measurement and detuned or filtered capacitor-bank review.