Motors, Contactors & Drives

Solid State Relay Selection & Heatsink Calculator

Calculate SSR load current, minimum nameplate-current screen, conduction loss, heatsink thermal resistance, junction temperature, surge margin, and semiconductor-fuse I²t checks.

Solid state relay electrical and thermal equations

SSR selection combines the load-current equation with manufacturer derating, conduction loss, a junction-to-ambient thermal network, and waveform-specific surge data.

Single phase or DC: Iload = P/(V × pf × η)
Three phase: Iload = P/(√3 × VLL × pf × η)
Current screen: ISSR,rated ≥ Iload / Fallowable
AC conduction loss: Ppole ≈ VON × Iload × duty
DC conduction loss: Ppole ≈ Iload² × RDS(on) × duty
RθSA,max = [TJ,max − TA − Ppole(RθJC + RθCS)] / Ptotal
TJ,estimate = TA + PtotalRθSA + Ppole(RθJC + RθCS)
Rectangular pulse screen: I²t ≈ Ipeak² × tpulse

where:

Fallowable
Allowable fraction of headline current from the exact datasheet derating curve
VON
Maximum SSR on-state voltage drop at the operating current[V]
RDS(on)
Maximum DC-output on resistance at operating junction temperature[Ω]
Ppole
Conduction loss in one output pole[W]
Ptotal
Total loss delivered to the common heatsink[W]
RθJC
Junction-to-case thermal resistance[°C/W]
RθCS
Case-to-sink interface thermal resistance[°C/W]
RθSA
Sink-to-air thermal resistance[°C/W]
TJ,max
Maximum permitted semiconductor junction temperature[°C]
TA
Air temperature immediately surrounding the heatsink[°C]

Use manufacturer power-loss and derating curves whenever available. A rectangular I²t estimate cannot be compared blindly with a half-sine datasheet rating or fuse value based on a different duration and initial temperature.

How to use the solid state relay calculator

Choose the workflow that matches the information available. Select an SSR converts load power or current into an electrical rating screen. Size a heatsink calculates conduction loss and the required thermal path. Check an existing SSR compares one candidate with current, voltage, surge, I²t, fuse, leakage, and minimum-load data entered from its datasheet.

  1. Choose SSR selection, heatsink sizing, or existing SSR verification.
  2. Identify AC or DC output and the real load type.
  3. Use measured load and inrush current whenever available.
  4. Enter worst-case datasheet values rather than typical values.
  5. Review every thermal and protection metric, not only the primary result.
  6. Verify the result against the exact VIOX or manufacturer datasheet before ordering.

AC SSR, DC SSR, and load compatibility

An AC-output SSR commonly uses a TRIAC or antiparallel thyristors and depends on AC current passing through zero to turn off. A DC-output SSR commonly uses a transistor or MOSFET. The output technology must match the load circuit; an ordinary AC TRIAC SSR is not a substitute for a DC-output SSR.

ApplicationStarting output choiceSwitching consideration
Resistive heaterAC TRIAC/SCR SSRZero-cross is commonly preferred for simple on/off temperature control
DC heater or valveDC MOSFET/transistor SSRCheck polarity, RDS(on), and inductive suppression
Motor or compressorMotor-rated AC or DC SSRStarting current, cycling, stall, phase loss, and bypass may govern
TransformerTransformer-load-rated SSRAsymmetric magnetizing inrush and turn-on point require special review
Incandescent or infrared lampLoad-compatible SSRCold-filament inrush can greatly exceed steady current
LED driver or capacitive inputLoad-compatible SSRShort charging pulses, minimum load, and leakage can govern

SSR current rating and temperature derating

The current printed on an SSR is conditional. Allowable continuous current depends on ambient or case temperature, heatsink, mounting orientation, spacing, airflow, thermal interface, and load category. The calculator therefore asks for an allowed datasheet current utilization instead of applying a universal two-times or six-times multiplier.

Use the allowable-current curve at the real ambient temperature

Headline current is not automatically the installed current

Adjacent SSRs and enclosed panels can require additional derating

SSR power loss and heatsink calculation

For an AC TRIAC or SCR output, a first thermal estimate uses on-state voltage multiplied by RMS load current. For a DC MOSFET output, conduction loss is current squared multiplied by maximum on resistance at operating temperature. The junction-to-case, interface, and heatsink thermal resistances then consume the available temperature rise from local air to maximum junction temperature.

Thermal termMeaningSelection note
RθJCJunction to SSR caseUse the exact datasheet maximum
RθCSCase through pad or compound to heatsinkDepends on interface material, flatness, pressure, and mounting
RθSAHeatsink to surrounding airDepends on heatsink, orientation, airflow, altitude, and enclosure
TJ,maxMaximum permitted semiconductor junction temperatureA design target may need margin below absolute maximum
TAAir immediately around the heatsinkUse internal panel temperature when mounted in an enclosure

SSR surge current and I²t verification

Motors, transformers, lamps, solenoids, and capacitive power supplies can have inrush far above continuous current. Compare the actual peak and duration with the SSR's non-repetitive and repetitive surge curves. I²t values are comparable only when waveform, duration, line frequency, repetition, and initial junction temperature use the same basis.

  • Use measured inrush or load-manufacturer data when possible.
  • Do not treat a one-cycle surge rating as a repetitive cycling rating.
  • A rectangular I²t estimate is not identical to a half-sine datasheet test.
  • Check commutating dv/dt and transient-voltage suppression for inductive loads.
  • Verify the permitted switching frequency and thermal cycling duty.

Semiconductor fuse and short-circuit coordination

An upstream breaker or general-purpose fuse may protect wiring without protecting an SSR semiconductor junction. The fuse total-clearing I²t must be coordinated with the SSR withstand using the manufacturer's approved table, voltage, prospective fault current, and safety margin. A simple fuse-I²t-below-SSR-I²t comparison is only an early screen.

Off-state leakage, minimum load, and safe isolation

An SSR is not an open mechanical contact. Off-state leakage can cause LED lamps to glow, sensitive loads to move or remain energized, and hazardous voltage to appear at the output. Many AC SSRs also require a minimum holding or load current. Most SSR failures are short-circuit failures, so the control system must define a safe response and provide mechanical isolation where required.

  • Do not use an SSR as the sole maintenance disconnect.
  • Check leakage at maximum load voltage and temperature.
  • Confirm the smallest connected load exceeds the specified minimum current.
  • Use manufacturer-approved snubbers or bleeders when needed.
  • Design diagnostics and shutdown behavior for a shorted SSR output.

Control panel thermal workflow

The SSR heatsink result supplies the heat released into the cabinet. Add that value to breakers, power supplies, drives, transformers, and other losses, then check enclosure temperature and cooling. The heatsink air temperature may be substantially higher than the room temperature.

Assumptions

  • Steady RMS or DC current for continuous thermal calculations
  • User-entered datasheet derating and thermal parameters
  • One common heatsink temperature for modules sharing a heatsink
  • Rectangular I²t estimate is shown only as a waveform-sensitive screen

Important Warnings

  • Preliminary engineering estimate only. Verify the final design against the current applicable standard, local rules, manufacturer data, and project conditions.
  • Final selection must use the exact SSR load category, derating curve, repetitive and non-repetitive surge data, thermal interface, mounting instructions, and coordinated semiconductor fuse.
  • An SSR can fail shorted, has off-state leakage, and is not a safe isolation device. Provide a suitable disconnect and protection architecture.

FAQ

Should I select an SSR by multiplying load current by two?

Not as a universal rule. Use the exact manufacturer's allowable-current curve at the real ambient, heatsink, mounting orientation, spacing, and load type. The utilization input makes that datasheet decision explicit.

Can an AC SSR switch a DC load?

A TRIAC or SCR AC-output SSR normally relies on AC current zero crossing to turn off and is not suitable for DC. Use a correctly rated DC-output MOSFET or transistor SSR.

When should I use zero-cross switching?

Zero-cross switching is commonly preferred for simple resistive heating to reduce switching EMI. Random or instantaneous turn-on is used for phase-angle control and some inductive applications, but transformer and motor inrush require exact application data.

Does an SSR provide electrical isolation when it is off?

No. Off-state leakage remains, and common failure mode can be short circuit. Use a mechanical disconnect or other required isolation means for safe maintenance.

Is the calculated heatsink resistance a part number?

No. It is the maximum sink-to-air thermal resistance under the entered simplified model. Select a heatsink from manufacturer curves for orientation, enclosure temperature, airflow, nearby devices, and mounting interface.