Copper Conductor Voltage Drop Chart & Table
Calculated with the existing voltage-drop calculator data: ρ = 0.0175 Ω·mm²/m at 20 °C, AWG area from conductorAreaToMm2(), and a two-wire path V = 2IρL/A for a one-way length of 100 ft. These are calculated values, not transcribed NEC table values.
Coverage: Copper 18 AWG–4/0 AWG; each row uses the existing AWG calculator reference current. One-way 100 ft; 120 V and 240 V percentage columns. No temperature correction, three-phase, aluminum or parallel-conductor rows.
The fixed current is a reference value from the existing AWG calculator, not a permitted ampacity for every installation. Apply the actual load, conductor temperature, installation corrections, power factor, phase system and project voltage-drop limit in the calculator.
Copper, one-way 100 ft
| AWG | Reference current (A) | Drop (V) | 120 V (%) | 240 V (%) |
|---|---|---|---|---|
| 18 | 5 | 6.48 | 5.4 | 2.7 |
| 16 | 10 | 8.15 | 6.8 | 3.4 |
| 14 | 15 | 7.69 | 6.4 | 3.2 |
| 12 | 20 | 6.45 | 5.4 | 2.7 |
| 10 | 30 | 6.08 | 5.1 | 2.5 |
| 8 | 40 | 5.10 | 4.3 | 2.1 |
| 6 | 55 | 4.41 | 3.7 | 1.8 |
| 4 | 70 | 3.53 | 2.9 | 1.5 |
| 3 | 85 | 3.40 | 2.8 | 1.4 |
| 2 | 95 | 3.01 | 2.5 | 1.3 |
| 1 | 110 | 2.77 | 2.3 | 1.2 |
| 1/0 | 125 | 3.14 | 2.6 | 1.3 |
| 2/0 | 145 | 4.60 | 3.8 | 1.9 |
| 3/0 | 165 | 6.60 | 5.5 | 2.7 |
| 4/0 | 195 | 9.84 | 8.2 | 4.1 |
How to use this chart
Find the conductor and read the fixed reference current, then compare the voltage-drop volts and percentage at the nominal system voltage. The absolute volts are unchanged by nominal voltage, while the percentage is halved from 120 V to 240 V.
Worked example
12 AWG at 20 A and one-way 100 ft: 6.45 V, or 5.4% at 120 V and 2.7% at 240 V. 10 AWG at 30 A: 6.08 V, or 5.1% at 120 V and 2.5% at 240 V.
Method & Sources
This is a reference chart; it does not run a calculator method.
Sources
- Existing voltage-drop calculator resistivity and AWG area dataEstimation basisValues are calculated from the calculator's stored rho and cross-sectional area data; no separate standards table is cited.
Related calculators
FAQ
What does this chart cover?
Copper 18 AWG–4/0 AWG; each row uses the existing AWG calculator reference current. One-way 100 ft; 120 V and 240 V percentage columns. No temperature correction, three-phase, aluminum or parallel-conductor rows.
Where do the values come from?
Calculated with the existing voltage-drop calculator data: ρ = 0.0175 Ω·mm²/m at 20 °C, AWG area from conductorAreaToMm2(), and a two-wire path V = 2IρL/A for a one-way length of 100 ft. These are calculated values, not transcribed NEC table values.
How do I read this chart?
Find the conductor and read the fixed reference current, then compare the voltage-drop volts and percentage at the nominal system voltage. The absolute volts are unchanged by nominal voltage, while the percentage is halved from 120 V to 240 V.
Can you show an example?
12 AWG at 20 A and one-way 100 ft: 6.45 V, or 5.4% at 120 V and 2.7% at 240 V. 10 AWG at 30 A: 6.08 V, or 5.1% at 120 V and 2.5% at 240 V.
What limits must I check?
The fixed current is a reference value from the existing AWG calculator, not a permitted ampacity for every installation. Apply the actual load, conductor temperature, installation corrections, power factor, phase system and project voltage-drop limit in the calculator.