Cable, Wire & Voltage Drop Tools

Copper Conductor Voltage Drop Chart & Table

Calculated with the existing voltage-drop calculator data: ρ = 0.0175 Ω·mm²/m at 20 °C, AWG area from conductorAreaToMm2(), and a two-wire path V = 2IρL/A for a one-way length of 100 ft. These are calculated values, not transcribed NEC table values.

Coverage: Copper 18 AWG–4/0 AWG; each row uses the existing AWG calculator reference current. One-way 100 ft; 120 V and 240 V percentage columns. No temperature correction, three-phase, aluminum or parallel-conductor rows.

The fixed current is a reference value from the existing AWG calculator, not a permitted ampacity for every installation. Apply the actual load, conductor temperature, installation corrections, power factor, phase system and project voltage-drop limit in the calculator.

Copper, one-way 100 ft

AWGReference current (A)Drop (V)120 V (%)240 V (%)
1856.485.42.7
16108.156.83.4
14157.696.43.2
12206.455.42.7
10306.085.12.5
8405.104.32.1
6554.413.71.8
4703.532.91.5
3853.402.81.4
2953.012.51.3
11102.772.31.2
1/01253.142.61.3
2/01454.603.81.9
3/01656.605.52.7
4/01959.848.24.1

How to use this chart

Find the conductor and read the fixed reference current, then compare the voltage-drop volts and percentage at the nominal system voltage. The absolute volts are unchanged by nominal voltage, while the percentage is halved from 120 V to 240 V.

Worked example

12 AWG at 20 A and one-way 100 ft: 6.45 V, or 5.4% at 120 V and 2.7% at 240 V. 10 AWG at 30 A: 6.08 V, or 5.1% at 120 V and 2.5% at 240 V.

Method & Sources

This is a reference chart; it does not run a calculator method.

Sources

  • Existing voltage-drop calculator resistivity and AWG area dataEstimation basisValues are calculated from the calculator's stored rho and cross-sectional area data; no separate standards table is cited.

Related calculators

FAQ

What does this chart cover?

Copper 18 AWG–4/0 AWG; each row uses the existing AWG calculator reference current. One-way 100 ft; 120 V and 240 V percentage columns. No temperature correction, three-phase, aluminum or parallel-conductor rows.

Where do the values come from?

Calculated with the existing voltage-drop calculator data: ρ = 0.0175 Ω·mm²/m at 20 °C, AWG area from conductorAreaToMm2(), and a two-wire path V = 2IρL/A for a one-way length of 100 ft. These are calculated values, not transcribed NEC table values.

How do I read this chart?

Find the conductor and read the fixed reference current, then compare the voltage-drop volts and percentage at the nominal system voltage. The absolute volts are unchanged by nominal voltage, while the percentage is halved from 120 V to 240 V.

Can you show an example?

12 AWG at 20 A and one-way 100 ft: 6.45 V, or 5.4% at 120 V and 2.7% at 240 V. 10 AWG at 30 A: 6.08 V, or 5.1% at 120 V and 2.5% at 240 V.

What limits must I check?

The fixed current is a reference value from the existing AWG calculator, not a permitted ampacity for every installation. Apply the actual load, conductor temperature, installation corrections, power factor, phase system and project voltage-drop limit in the calculator.