Circuit Protection & Grounding

Assembly SCCR Calculator

Find the weakest entered power-circuit component and the unenhanced assembly SCCR. Use verified ratings or the documented terminal-block default.

UL 508A Supplement SB

Assembly SCCR Calculator

All entered ratings apply at the system voltage and satisfy their protection conditions. No current-limiting or tested-combination enhancement is applied.

SCCR = min(SCCR₁, SCCR₂, …, SCCRₙ)

where:

SCCR
Unenhanced assembly short-circuit current rating[kA]
SCCRₙ
Verified rating of each applicable component[kA]

Calculation basis

Find the weakest entered power-circuit component and the unenhanced assembly SCCR. Use verified ratings or the documented terminal-block default.

All entered ratings apply at the system voltage and satisfy their protection conditions. No current-limiting or tested-combination enhancement is applied.

Verified tables and sources

Only the 10 kA terminal-block value documented against UL 508A Table SB4.1 by Weidmuller. Confirm component eligibility and applicable edition.

ParameterValue
Terminal block10 kA

Worked examples

The unenhanced assembly SCCR is 10 kA; the component rated 10 kA is the weakest.

If another component is also 10 kA, both names appear as weak links. An unverified component prevents a numerical result until its rating is established.

Method & Sources

Method

Formula used

  • SCCR = min(SCCR₁, SCCR₂, …, SCCRₙ)

Input basis

All entered ratings apply at the system voltage and satisfy their protection conditions. No current-limiting or tested-combination enhancement is applied.

  • Number of components
  • Component 1 name
  • Component 1 rating source
  • Component 1 marked SCCR [kA]
  • Component 2 name
  • Component 2 rating source
  • Component 2 marked SCCR [kA]
  • Component 3 name
  • Component 3 rating source
  • Component 3 marked SCCR [kA]
  • Component 4 name
  • Component 4 rating source
  • Component 4 marked SCCR [kA]
  • Component 5 name
  • Component 5 rating source
  • Component 5 marked SCCR [kA]
  • Component 6 name
  • Component 6 rating source
  • Component 6 marked SCCR [kA]
  • Component 7 name
  • Component 7 rating source
  • Component 7 marked SCCR [kA]
  • Component 8 name
  • Component 8 rating source
  • Component 8 marked SCCR [kA]
  • Component 9 name
  • Component 9 rating source
  • Component 9 marked SCCR [kA]
  • Component 10 name
  • Component 10 rating source
  • Component 10 marked SCCR [kA]
  • Component 11 name
  • Component 11 rating source
  • Component 11 marked SCCR [kA]
  • Component 12 name
  • Component 12 rating source
  • Component 12 marked SCCR [kA]
  • Component 13 name
  • Component 13 rating source
  • Component 13 marked SCCR [kA]
  • Component 14 name
  • Component 14 rating source
  • Component 14 marked SCCR [kA]
  • Component 15 name
  • Component 15 rating source
  • Component 15 marked SCCR [kA]
  • Component 16 name
  • Component 16 rating source
  • Component 16 marked SCCR [kA]
  • Component 17 name
  • Component 17 rating source
  • Component 17 marked SCCR [kA]
  • Component 18 name
  • Component 18 rating source
  • Component 18 marked SCCR [kA]
  • Component 19 name
  • Component 19 rating source
  • Component 19 marked SCCR [kA]
  • Component 20 name
  • Component 20 rating source
  • Component 20 marked SCCR [kA]
  • SCCR — Unenhanced assembly short-circuit current rating [kA]
  • SCCRₙ — Verified rating of each applicable component [kA]

Units

kA

Display and rounding

No separate display or rounding rule is stated on this page.

Scope and limits

  • All entered ratings apply at the system voltage and satisfy their protection conditions. No current-limiting or tested-combination enhancement is applied.
  • This is a conservative baseline screen, not the complete UL 508A Supplement SB procedure or a certification. An omitted or wrongly rated component invalidates the result.

Sources

Application limits

This is a conservative baseline screen, not the complete UL 508A Supplement SB procedure or a certification. An omitted or wrongly rated component invalidates the result.

No. Interrupting capacity alone does not establish a higher assembly SCCR. Current-limiting and tested combinations need separate documented evaluation.

Assumptions

  • All entered ratings apply at the system voltage and satisfy their protection conditions. No current-limiting or tested-combination enhancement is applied.

Important Warnings

  • This is a conservative baseline screen, not the complete UL 508A Supplement SB procedure or a certification. An omitted or wrongly rated component invalidates the result.

FAQ

What is the result for 65, 25 and 10 kA?

The unenhanced assembly SCCR is 10 kA; the component rated 10 kA is the weakest.

What if several components share the minimum?

Every component with the minimum entered rating is listed as a weak link.

What happens to an unmarked component?

Calculation stops until you enter a verified rating or select an applicable documented default. An unknown rating is never silently ignored.

Which default is included?

Only the 10 kA terminal-block value documented against UL 508A Table SB4.1 by Weidmuller. Confirm component eligibility and applicable edition.

Can a high-rated fuse raise this result automatically?

No. Interrupting capacity alone does not establish a higher assembly SCCR. Current-limiting and tested combinations need separate documented evaluation.