IDMT Relay Trip-Time Calculator

Calculate IEC 60255 standard, very, and extremely inverse relay trip times, then compare upstream and downstream grading margin against 0.30 seconds.

IEC 60255

IEC 60255 IDMT equations

The selected curve and TMS determine relay operating time at the fault-to-pickup ratio.

Standard Inverse
tSI = 0.14 TMS / [(I/Is)^0.02 − 1]
Very Inverse
tVI = 13.5 TMS / [(I/Is) − 1]
Extremely Inverse
tEI = 80 TMS / [(I/Is)^2 − 1]
Grading margin
Δtg = tupstream − tdownstream

where:

I
Fault current[A]
Is
Relay pickup current[A]
TMS
Time multiplier setting
t
Relay trip time[s]

For Standard Inverse at 14 times pickup, TMS 0.30 gives 0.78 s and TMS 0.15 gives 0.39 s, leaving a passing 0.39 s margin.

How to calculate IDMT relay trip time

Divide fault current by pickup current, select the IEC curve, and apply TMS to the curve equation. The time is the relay operating target before additional coordination allowances.

  1. Select Standard, Very, or Extremely Inverse.
  2. Enter pickup current, fault current, and both TMS values.
  3. Review up/downstream times and margin.
  4. Confirm relay-specific curves and tolerances.

Worked Standard Inverse example

For Is = 400 A, I = 5,600 A, and I/Is = 14, upstream TMS 0.30 gives about 0.78 s and downstream TMS 0.15 gives about 0.39 s. The resulting 0.39 s margin passes the 0.30 s target.

CurveFormulaUse
Standard Inverset = 0.14 TMS / [(I/Is)^0.02 − 1]General overcurrent grading
Very Inverset = 13.5 TMS / [(I/Is) − 1]Faster at high fault current
Extremely Inverset = 80 TMS / [(I/Is)^2 − 1]Steep inverse characteristic

Method & Sources

Method

Formula used

  • tSI = 0.14 TMS / [(I/Is)^0.02 − 1]
  • tVI = 13.5 TMS / [(I/Is) − 1]
  • tEI = 80 TMS / [(I/Is)^2 − 1]
  • Δtg = tupstream − tdownstream

Input basis

The selected curve and TMS determine relay operating time at the fault-to-pickup ratio.

  • IEC inverse-time curve
  • Pickup current Is [A]
  • Fault current I [A]
  • Upstream TMS
  • Downstream TMS
  • Required grading margin [s]
  • I — Fault current [A]
  • Is — Relay pickup current [A]
  • TMS — Time multiplier setting
  • t — Relay trip time [s]

Units

A · s

Display and rounding

No separate display or rounding rule is stated on this page.

Scope and limits

  • The relay follows the stated IEC 60255 equation constants and the fault current is steady during the calculated trip interval.
  • Upstream and downstream relays use the same curve and pickup current in the grading comparison.
  • Grading margin equals upstream trip time minus downstream trip time at the entered fault current.
  • Relay tolerance, CT error, saturation, breaker opening time, arc time, reset ratio, and fault X/R ratio can change the required setting.
  • This is not a complete protection coordination study or proof of selective operation across the full fault-current range.
  • For Standard Inverse at 14 times pickup, TMS 0.30 gives 0.78 s and TMS 0.15 gives 0.39 s, leaving a passing 0.39 s margin.

Sources

  • IEC 60255, inverse-time overcurrent relay equationsEdition not stated on this page; clause and table identifiers are preserved verbatim.

Coordination and CT checks

Use short-circuit current and CT burden tools to establish the current seen by each relay and confirm that the CT remains suitable over the grading range.

Why the margin needs a full study

A calculated time difference is not proof of selectivity. Relay tolerance, CT performance, breaker clearing, arc duration, reset, and the full current range must be included.

Assumptions

  • The relay follows the stated IEC 60255 equation constants and the fault current is steady during the calculated trip interval.
  • Upstream and downstream relays use the same curve and pickup current in the grading comparison.
  • Grading margin equals upstream trip time minus downstream trip time at the entered fault current.

Important Warnings

  • Relay tolerance, CT error, saturation, breaker opening time, arc time, reset ratio, and fault X/R ratio can change the required setting.
  • This is not a complete protection coordination study or proof of selective operation across the full fault-current range.

FAQ

Why is the upstream trip time 0.78 s?

For Standard Inverse, I/Is = 14 and TMS = 0.30. The calculated time is about 0.7749 s, rounded up conservatively to 0.78 s.

Why is the grading margin 0.39 s?

The downstream time is about 0.3875 s. Subtracting it from the upstream time gives a margin of about 0.3875 s, displayed as 0.39 s.

Does a 0.30 s margin guarantee selectivity?

No. It is one screening target. Final coordination must include equipment tolerances and the complete current range.

What happens when fault current is below pickup?

The inverse-time equation is not evaluated. The calculator requires fault current above pickup because the relay is not expected to start.

Why compare it with the relay datasheet?

Some relays implement additional curve constants, time dials, definite-time elements, or restricted ranges. Use the selected product's certified curve data.