Battery Charger Sizing Calculator (IEEE 946)

Size a stationary battery charger from continuous DC load, discharged Ah, recharge time, and the largest noncontinuous load using the IEEE 946 method.

IEEE 946

IEEE 946 charger-current equations

The larger of the recharge-current and simultaneous-load paths establishes the minimum charger output.

I1
I1 = LC + 1.1 × Q / T
I2
I2 = LC + ILN
Required rating
Icharger = max(I1, I2)

where:

LC
Continuous DC load[A]
Q
Discharged capacity[Ah]
T
Recharge time[h]
ILN
Largest noncontinuous load combination[A]

For LC 25 A, Q 125 Ah, T 8 h, and ILN 10 A: I1 = 42.2 A, I2 = 35 A, and the next planning class is 45 A.

How to apply the IEEE 946 method

Enter the continuous DC load, the Ah discharged from the battery, the desired recharge time, and the largest noncontinuous load combination. The calculator evaluates both current paths and takes the larger value.

  1. Determine LC from the continuous DC load schedule.
  2. Enter Q and the project recharge time T.
  3. Enter ILN for the largest simultaneous noncontinuous load.
  4. Select a manufacturer rating at or above the result.

Worked example: 42.2 A charger

With LC 25 A, Q 125 Ah, T 8 h, and ILN 10 A: I1 = 25 + 1.1 × 125 / 8 = 42.2 A and I2 = 25 + 10 = 35 A. The required charger output is 42.2 A; the next value in the disclosed planning list is 45 A.

I1 42.2 A > I2 35 A → 45 A planning class

LCQTILNI1I2Planning class
25 A125 Ah8 h10 A42.2 A35 A45 A

Method & Sources

Method

Formula used

  • I1 = LC + 1.1 × Q / T
  • I2 = LC + ILN
  • Icharger = max(I1, I2)

Input basis

The larger of the recharge-current and simultaneous-load paths establishes the minimum charger output.

  • Continuous DC load (LC) [A]
  • Discharged capacity (Q) [Ah]
  • Recharge time (T) [h]
  • Largest noncontinuous load combination (ILN) [A]
  • LC — Continuous DC load [A]
  • Q — Discharged capacity [Ah]
  • T — Recharge time [h]
  • ILN — Largest noncontinuous load combination [A]

Units

A · Ah · h

Display and rounding

  • The internal planning list is 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 75, 100, 125, 150, 200 A. It is shown to make the rounding step transparent; it is not an IEEE 946 standard series.

Scope and limits

  • LC is the continuous direct-current load that remains during recharge.
  • Q is the ampere-hours actually removed from the battery and T is the desired recharge time.
  • The 1.1 factor accounts for recharge losses as a planning coefficient.
  • The 45 A recommended value is from an internal planning list, not an IEEE 946 standard rating table.
  • Verify the applicable IEEE 946 edition, battery recharge acceptance, current limit, float voltage, temperature compensation, and manufacturer ratings.
  • For LC 25 A, Q 125 Ah, T 8 h, and ILN 10 A: I1 = 42.2 A, I2 = 35 A, and the next planning class is 45 A.

Sources

  • IEEE 946, stationary battery charger methodEdition not stated on this page; clause and table identifiers are preserved verbatim.

Planning rating list

The internal planning list is 10, 15, 20, 25, 30, 35, 40, 45, 50, 60, 75, 100, 125, 150, 200 A. It is shown to make the rounding step transparent; it is not an IEEE 946 standard series.

Continue the stationary DC workflow

Use the linked tools to check the battery bank, ideal charging time, and UPS runtime before selecting protection and conductors.

Assumptions

  • LC is the continuous direct-current load that remains during recharge.
  • Q is the ampere-hours actually removed from the battery and T is the desired recharge time.
  • The 1.1 factor accounts for recharge losses as a planning coefficient.

Important Warnings

  • The 45 A recommended value is from an internal planning list, not an IEEE 946 standard rating table.
  • Verify the applicable IEEE 946 edition, battery recharge acceptance, current limit, float voltage, temperature compensation, and manufacturer ratings.

FAQ

What does the 1.1 coefficient represent?

It is the recharge-loss allowance in I1 = LC + 1.1 × Q / T, applied to the discharged ampere-hours.

Why calculate two paths?

A charger may be governed by restoring battery charge or by serving the continuous load plus the largest noncontinuous load. The larger result governs.

Is 45 A an IEEE standard size?

No. It is the next value in the disclosed internal planning list; select a real charger series that meets or exceeds the required current.

What is ILN?

ILN is the largest combination of noncontinuous direct-current loads that can occur while the charger is operating.

Can I change the recharge time?

Yes. Enter the project recharge time T; a shorter T increases I1 and may increase the required charger rating.