Solar, Battery & Backup Power

Solar Battery Bank Size Calculator

Calculate solar battery bank kWh, Ah, and battery quantity from daily energy, autonomy days, depth of discharge, system voltage, and battery capacity.

Solar battery bank equations

Autonomy increases the usable energy requirement; depth of discharge increases nominal capacity.

Eusable = Edaily × Nautonomy
Enominal = Eusable / DoD
Qbank = 1000 × Enominal / Vbank
Nbattery = ceil(Qbank / Qbattery)

where:

Edaily
Daily energy use[kWh]
Nautonomy
Days of autonomy[days]
DoD
Depth of discharge[%]
Vbank
Battery-bank voltage[V]
Qbattery
Capacity per battery block[Ah]

The example gives 12.5 kWh nominal storage, about 260 Ah, and three 100 Ah blocks.

How to calculate solar battery bank capacity

Multiply daily energy by autonomy days to find usable energy, divide by depth of discharge to obtain nominal energy, and convert nominal energy to Ah at the bank voltage.

  1. Enter representative daily energy.
  2. Choose the required days without solar charging.
  3. Use the battery datasheet DoD and nominal bank voltage.
  4. Round discrete battery blocks upward.

Worked 5 kWh, two-day example

At 80% DoD, 10 kWh usable energy requires 12.5 kWh nominal storage. At 48 V this is about 260 Ah, requiring three 100 Ah battery blocks.

QuantityResult
Usable energy10 kWh
Nominal storage12.5 kWh
Bank capacity260 Ah
48 V 100 Ah blocks3

Method & Sources

Method

Formula used

  • Eusable = Edaily × Nautonomy
  • Enominal = Eusable / DoD
  • Qbank = 1000 × Enominal / Vbank
  • Nbattery = ceil(Qbank / Qbattery)

Input basis

Autonomy increases the usable energy requirement; depth of discharge increases nominal capacity.

  • Daily energy use [kWh]
  • Days of autonomy [days]
  • Depth of discharge [%]
  • Battery bank voltage [V]
  • Capacity per battery block [Ah]
  • Edaily — Daily energy use [kWh]
  • Nautonomy — Days of autonomy [days]
  • DoD — Depth of discharge [%]
  • Vbank — Battery-bank voltage [V]
  • Qbattery — Capacity per battery block [Ah]

Units

kWh · days · % · V · Ah

Display and rounding

  • Round discrete battery blocks upward.

Scope and limits

  • Each battery block is assumed to operate at the entered battery-bank voltage.
  • Depth of discharge is the fraction of nominal capacity intended to be used before recharge.
  • The result does not model temperature derating, aging, inverter cut-off, or charge efficiency.
  • Verify the battery datasheet DoD, continuous and peak current, temperature limits, and series/parallel topology.
  • Battery voltage varies with chemistry and state of charge; system-level protection and charging must match the complete battery specification.
  • The example gives 12.5 kWh nominal storage, about 260 Ah, and three 100 Ah blocks.

Sources

  • Estimation basis: published page formula, assumptions, and warningsEstimation basisNo separate public standard is cited; the published equation and stated input scope form a planning or screening basis.

Battery topology and operating limits

The screenshot example assumes 48 V battery blocks in parallel. A different block voltage requires an explicit series/parallel design. Verify current limits and BMS behavior before construction.

Temperature, aging, and autonomy

A bank that passes at beginning of life may lose usable capacity when cold or aged. Confirm the manufacturer's capacity at the lowest operating temperature and the end-of-life criterion.

Assumptions

  • Each battery block is assumed to operate at the entered battery-bank voltage.
  • Depth of discharge is the fraction of nominal capacity intended to be used before recharge.
  • The result does not model temperature derating, aging, inverter cut-off, or charge efficiency.

Important Warnings

  • Verify the battery datasheet DoD, continuous and peak current, temperature limits, and series/parallel topology.
  • Battery voltage varies with chemistry and state of charge; system-level protection and charging must match the complete battery specification.

FAQ

Why is the required storage 12.5 kWh?

The load needs 5 kWh per day for two days, or 10 kWh usable. At 80% DoD, nominal capacity is 10 / 0.80 = 12.5 kWh.

Why does 12.5 kWh require three 48 V 100 Ah batteries?

The required capacity is about 260 Ah. One 100 Ah block is too small and two provide only 200 Ah, so three blocks are required in the assumed parallel arrangement.

Does a higher DoD reduce battery quantity?

Mathematically yes, but the allowed DoD must come from the battery manufacturer and the required cycle life. The tool does not increase DoD automatically.

Why is installed capacity larger than required capacity?

Battery blocks are discrete. Three 100 Ah blocks provide 300 Ah, rounded up from the calculated 260.4 Ah requirement.

Is this the same as UPS backup time?

No. This page sizes nominal bank energy. Runtime also depends on discharge current, inverter efficiency, voltage cutoff, battery aging, and the load profile.