PV DC voltage-drop equations
The design current applies 1.25 times Isc and the resistance includes both circuit conductors.
Idesign = 1.25 × IscVdrop = 2 × ρ × L × Idesign / ADrop(%) = 100 × Vdrop / VmpPASS when Drop(%) ≤ 2%where:
- Isc
- String short-circuit current[A]
- ρ
- Copper resistivity[Ω·mm²/m]
- L
- One-way cable length[m]
- A
- Conductor area[mm²]
- Vmp
- String voltage at maximum power[V]
At 13 A Isc, 30 m, 200 V, and copper conductor, 4 mm² gives 2.1% and 6 mm² gives 1.4%.
How to calculate PV DC voltage drop
The design current is 125% of string Isc. The two-wire voltage drop uses the outgoing-and-return length through copper resistance, then divides by string Vmp for the percentage.
- Enter string Isc and Vmp.
- Enter the physical one-way cable length.
- Select the copper conductor size.
- Compare the result with the 2% DC target.
Worked 4 mm² and 6 mm² comparison
At 16.25 A design current, 30 m one-way, and 200 V Vmp, 4 mm² copper produces 4.27 V and fails; 6 mm² produces 2.84 V and passes.
| Copper size | Voltage drop | Percentage | Result |
|---|---|---|---|
| 4 mm² | 4.27 V | 2.1% | FAIL |
| 6 mm² | 2.84 V | 1.4% | PASS |
Method & Sources
Method
Formula used
Idesign = 1.25 × IscVdrop = 2 × ρ × L × Idesign / ADrop(%) = 100 × Vdrop / VmpPASS when Drop(%) ≤ 2%
Input basis
The design current applies 1.25 times Isc and the resistance includes both circuit conductors.
- String Isc [A]
- One-way cable length [m]
- String Vmp [V]
- Copper conductor size
- Isc — String short-circuit current [A]
- ρ — Copper resistivity [Ω·mm²/m]
- L — One-way cable length [m]
- A — Conductor area [mm²]
- Vmp — String voltage at maximum power [V]
Units
A · m · V · Ω·mm²/m · mm²
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- The circuit is a two-wire copper DC run and one-way length is entered.
- Copper resistivity is 0.0175 Ω·mm²/m at 20 °C, shared with the site DC voltage-drop basis.
- The 2% limit is a design target on this page; confirm inverter and project requirements.
- Use hot-conductor resistance and include terminals, fuses, connectors, and junction losses for final cable design.
- Voltage drop does not establish cable current-carrying capacity, short-circuit withstand, or DC isolator rating.
- At 13 A Isc, 30 m, 200 V, and copper conductor, 4 mm² gives 2.1% and 6 mm² gives 1.4%.
Sources
- NFPA 70, National Electrical Code (NEC), 690.8Edition not stated on this page; clause and table identifiers are preserved verbatim.
Cable and system checks
Voltage drop is separate from cable ampacity, short-circuit temperature rise, maximum DC voltage, isolation, and pull tension.
Temperature and connection losses
The displayed values use 20 °C copper resistivity. Hot conductors have higher resistance, and connectors, fuses, and isolators add additional voltage loss.
Assumptions
- The circuit is a two-wire copper DC run and one-way length is entered.
- Copper resistivity is 0.0175 Ω·mm²/m at 20 °C, shared with the site DC voltage-drop basis.
- The 2% limit is a design target on this page; confirm inverter and project requirements.
Important Warnings
- Use hot-conductor resistance and include terminals, fuses, connectors, and junction losses for final cable design.
- Voltage drop does not establish cable current-carrying capacity, short-circuit withstand, or DC isolator rating.