Solar, Battery & Backup Power

Voltage Rise Calculator

Calculate grid-tied inverter voltage rise from export current, complete loop resistance, and nominal voltage, with a 2% AS/NZS 4777 screening check.

AS/NZS 4777

Grid voltage-rise equations

Export current flowing through loop resistance raises the voltage at the inverter terminals.

Vrise = Igrid × Rloop
Vrise(%) = 100 × Vrise / Vnominal
PASS when Vrise(%) ≤ 2%

where:

Igrid
Maximum export current[A]
Rloop
Complete loop resistance[Ω]
Vnominal
Nominal grid voltage[V]

At 32 A and 230 V, 0.15 Ω gives 2.1% and 0.10 Ω gives 1.4%.

How to calculate grid voltage rise

Multiply export current by total loop resistance, then divide by nominal voltage to express the result as a percentage.

  1. Enter maximum export current.
  2. Enter the complete outgoing-and-return resistance.
  3. Enter nominal voltage and compare with 2%.
  4. Confirm the local network operator limit.

Worked 32 A, 230 V example

At 0.15 Ω the rise is 4.8 V and 2.1%, which fails this page's 2% screening. At 0.10 Ω the rise is 3.2 V and 1.4%, which passes.

Loop resistanceRisePercentageResult
0.15 Ω4.8 V2.1%FAIL
0.10 Ω3.2 V1.4%PASS

Method & Sources

Method

Formula used

  • Vrise = Igrid × Rloop
  • Vrise(%) = 100 × Vrise / Vnominal
  • PASS when Vrise(%) ≤ 2%

Input basis

Export current flowing through loop resistance raises the voltage at the inverter terminals.

  • Grid export current [A]
  • Complete loop resistance [Ω]
  • Nominal grid voltage [V]
  • Igrid — Maximum export current [A]
  • Rloop — Complete loop resistance [Ω]
  • Vnominal — Nominal grid voltage [V]

Units

A · Ω · V

Display and rounding

No separate display or rounding rule is stated on this page.

Scope and limits

  • Loop resistance already includes the outgoing and return conductor paths plus relevant source impedance.
  • The grid current represents the maximum export condition being checked.
  • The page uses 2% as an AS/NZS 4777 screening context, not as a universal network limit.
  • The local network operator may publish a different voltage-rise limit, measurement point, or calculation method.
  • Use hot-conductor resistance and the actual shared feeder impedance for final design.
  • At 32 A and 230 V, 0.15 Ω gives 2.1% and 0.10 Ω gives 1.4%.

Sources

  • AS/NZS 4777, grid-connected inverter voltage-rise screening contextEdition not stated on this page; clause and table identifiers are preserved verbatim.

Voltage-drop and inverter checks

Voltage rise and voltage drop describe opposite operating directions. Also verify inverter sizing, maximum export current, and feeder loading.

Network-specific voltage limits

The 2% value is a planning context associated with AS/NZS 4777 on this page. Network operators can impose different measurements and limits, so the adopted connection rule always wins.

Assumptions

  • Loop resistance already includes the outgoing and return conductor paths plus relevant source impedance.
  • The grid current represents the maximum export condition being checked.
  • The page uses 2% as an AS/NZS 4777 screening context, not as a universal network limit.

Important Warnings

  • The local network operator may publish a different voltage-rise limit, measurement point, or calculation method.
  • Use hot-conductor resistance and the actual shared feeder impedance for final design.

FAQ

Why is 0.15 Ω a fail in the example?

At 32 A and 230 V, 0.15 Ω produces 4.8 V, or 2.1%. The result exceeds the page's 2% screening limit.

Why does 0.10 Ω pass?

The same current across 0.10 Ω gives 3.2 V, or 1.4% of 230 V, which is below 2%.

What resistance should I enter?

Enter the complete loop resistance from the inverter through the shared electrical path and back. Do not enter only one conductor.

Is 2% always the grid limit?

No. The page uses 2% for consistency with the stated AS/NZS 4777 context. Always verify the network operator's current connection requirements.

Is voltage rise the same as voltage drop?

They use the same impedance relationship but opposite direction. Voltage drop reduces voltage along a load current path; voltage rise raises local voltage during export.