Grid voltage-rise equations
Export current flowing through loop resistance raises the voltage at the inverter terminals.
Vrise = Igrid × RloopVrise(%) = 100 × Vrise / VnominalPASS when Vrise(%) ≤ 2%where:
- Igrid
- Maximum export current[A]
- Rloop
- Complete loop resistance[Ω]
- Vnominal
- Nominal grid voltage[V]
At 32 A and 230 V, 0.15 Ω gives 2.1% and 0.10 Ω gives 1.4%.
How to calculate grid voltage rise
Multiply export current by total loop resistance, then divide by nominal voltage to express the result as a percentage.
- Enter maximum export current.
- Enter the complete outgoing-and-return resistance.
- Enter nominal voltage and compare with 2%.
- Confirm the local network operator limit.
Worked 32 A, 230 V example
At 0.15 Ω the rise is 4.8 V and 2.1%, which fails this page's 2% screening. At 0.10 Ω the rise is 3.2 V and 1.4%, which passes.
| Loop resistance | Rise | Percentage | Result |
|---|---|---|---|
| 0.15 Ω | 4.8 V | 2.1% | FAIL |
| 0.10 Ω | 3.2 V | 1.4% | PASS |
Method & Sources
Method
Formula used
Vrise = Igrid × RloopVrise(%) = 100 × Vrise / VnominalPASS when Vrise(%) ≤ 2%
Input basis
Export current flowing through loop resistance raises the voltage at the inverter terminals.
- Grid export current [A]
- Complete loop resistance [Ω]
- Nominal grid voltage [V]
- Igrid — Maximum export current [A]
- Rloop — Complete loop resistance [Ω]
- Vnominal — Nominal grid voltage [V]
Units
A · Ω · V
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- Loop resistance already includes the outgoing and return conductor paths plus relevant source impedance.
- The grid current represents the maximum export condition being checked.
- The page uses 2% as an AS/NZS 4777 screening context, not as a universal network limit.
- The local network operator may publish a different voltage-rise limit, measurement point, or calculation method.
- Use hot-conductor resistance and the actual shared feeder impedance for final design.
- At 32 A and 230 V, 0.15 Ω gives 2.1% and 0.10 Ω gives 1.4%.
Sources
- AS/NZS 4777, grid-connected inverter voltage-rise screening contextEdition not stated on this page; clause and table identifiers are preserved verbatim.
Voltage-drop and inverter checks
Voltage rise and voltage drop describe opposite operating directions. Also verify inverter sizing, maximum export current, and feeder loading.
Network-specific voltage limits
The 2% value is a planning context associated with AS/NZS 4777 on this page. Network operators can impose different measurements and limits, so the adopted connection rule always wins.
Assumptions
- Loop resistance already includes the outgoing and return conductor paths plus relevant source impedance.
- The grid current represents the maximum export condition being checked.
- The page uses 2% as an AS/NZS 4777 screening context, not as a universal network limit.
Important Warnings
- The local network operator may publish a different voltage-rise limit, measurement point, or calculation method.
- Use hot-conductor resistance and the actual shared feeder impedance for final design.