Lighting calculation equations
The lumen method estimates average maintained illuminance from room area, fixture output, utilization, and maintenance conditions.
Φrequired = E × A / (UF × MF)N = ceil(Φrequired / Φfixture)Einstalled = N × Φfixture × UF × MF / AI = N × Pfixture / (V × pf)where:
- Φrequired
- Fixture lumens required before utilization and maintenance losses[lm]
- E
- Target or achieved maintained illuminance[lx]
- A
- Illuminated area[m²]
- UF
- Utilization factor
- MF
- Maintenance factor
- N
- Whole number of fixtures
- Φfixture
- Rated luminous flux per fixture[lm]
- Pfixture
- Input power per fixture[W]
- I
- Steady-state lighting current[A]
A lumen-method result does not prove uniformity, glare control, emergency-lighting compliance, or LED-driver inrush compatibility.
How to use the Lighting Calculator: Lux, Lumens and Fixtures
Choose the space or task to load a broad starting illuminance value, or enter custom lux from the applicable project requirement. Add the room dimensions, utilization and maintenance factors, and the exact fixture lumen and watt ratings. The result connects the lighting requirement to fixture quantity and electrical circuit load.
- Choose a space preset or custom maintained illuminance.
- Enter room dimensions or illuminated area.
- Enter utilization and maintenance factors from project data.
- Enter rated lumens, watts, voltage, and power factor for one fixture.
- Review fixture quantity, achieved lux, connected load, current, and preliminary circuit count.
Calculation method and validation
The equations and symbol definitions above show the complete calculation basis. Inputs are checked before calculation so zero, negative, incompatible, or physically impossible combinations are flagged instead of silently producing a misleading result.
How to interpret the result
Use the main result as a starting value and read every supporting metric. Average maintained illuminance over the entered area Uniform fixture distribution and representative utilization factor Balanced fixture loading where more than one circuit or phase is used A passing or recommended result means the entered mathematical conditions are satisfied; it does not certify the complete installation or a particular product combination.
- Average maintained illuminance over the entered area
- Uniform fixture distribution and representative utilization factor
- Balanced fixture loading where more than one circuit or phase is used
Selection limits and next checks
Preliminary engineering estimate only. Verify the final design against the current applicable standard, local rules, manufacturer data, and project conditions. The preset lux values are broad planning references, not a substitute for the applicable workplace, emergency-lighting, local energy, or project standard. LED-driver inrush current and maximum devices per MCB may govern circuit count even when steady-state current is low. Compare the output with the current applicable standard, local rules, exact VIOX product datasheet, environmental conditions, protection coordination, and the engineer's project requirements before procurement or installation.
Continue with energy cost calculatorContinue with maximum demand calculatorContinue with mcb inrush compatibility checker
Assumptions
- Average maintained illuminance over the entered area
- Uniform fixture distribution and representative utilization factor
- Balanced fixture loading where more than one circuit or phase is used
Important Warnings
- Preliminary engineering estimate only. Verify the final design against the current applicable standard, local rules, manufacturer data, and project conditions.
- The preset lux values are broad planning references, not a substitute for the applicable workplace, emergency-lighting, local energy, or project standard.
- LED-driver inrush current and maximum devices per MCB may govern circuit count even when steady-state current is low.