AFDD rating and function checks
AFDD selection combines a local requirement review with independent current, voltage, residual-current, and short-circuit checks.
Ib <= InUe >= U0Icn >= IkIΔn = selected residual operating currentwhere:
- Ib
- Circuit design current[A]
- In
- AFDD rated current[A]
- Ue
- Rated operational voltage[V]
- Ik
- Prospective short-circuit current[kA]
- IΔn
- Rated residual operating current[mA]
The equations screen ratings only. Whether AFDD protection is required is determined by current local rules and the project risk assessment.
How to use the AFDD selection calculator
Choose the project rules basis, premises, and circuit type, then enter the circuit voltage, design current, candidate rating, characteristic, residual sensitivity, and prospective short-circuit current. Read the local-rules status separately from the product-envelope check.
- Confirm whether the project is governed by IEC/EN, UK, EU, or another local adoption.
- Enter the circuit design current and fault level.
- Choose the required B or C characteristic and Type A sensitivity.
- Review every pass/fail line rather than relying only on the model-family result.
What an AFDD protects against
An AFDD detects current signatures associated with hazardous arc faults. An integrated AFDD-RCBO can also provide residual-current, overload, and short-circuit functions, but each function retains its own marked rating and standard.
- Series arc current may remain below a conventional breaker magnetic threshold.
- An RCD detects residual current but is not a general series-arc detector.
- AFDD application rules vary by jurisdiction, premises, circuit, and adopted standard edition.
VIOX AFDD configuration screen
The product screen uses the published VAF1-40 and VAF3-40M envelope: 240 V AC, 1P+N, 6-40 A, B or C characteristic, Type A 10 or 30 mA, and 6 kA short-circuit rating. A pass means the entered values fit that envelope; it is not a declaration of legal compliance.
Check circuit breaker sizeSelect an RCD or RCBOCalculate prospective fault current
AFDD selection example
For a 230 V residential socket circuit with 24 A design current, a 32 A C-curve, Type A 30 mA candidate can fit the published VIOX electrical envelope when prospective fault current remains below 6 kA. The project must still establish whether AFDD protection is required and whether every circuit and installation condition is acceptable.
Method & Sources
Method
Formula used
Ib <= InUe >= U0Icn >= IkIΔn = selected residual operating current
Input basis
AFDD selection combines a local requirement review with independent current, voltage, residual-current, and short-circuit checks.
- Region / rules basis
- Premises / risk context
- Final-circuit use
- Circuit voltage [V AC]
- Design current [A]
- Candidate rated current
- Overcurrent characteristic
- Type A residual sensitivity
- Prospective short-circuit current [kA]
- Ib — Circuit design current [A]
- In — AFDD rated current [A]
- Ue — Rated operational voltage [V]
- Ik — Prospective short-circuit current [kA]
- IΔn — Rated residual operating current [mA]
Units
V AC · A · kA · V · mA
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- VIOX VAF1-40 and VAF3-40M published envelope: 240 V AC, 1P+N, 6-40 A, B/C, Type A 10/30 mA, 6 kA
- Final circuit supplied line-to-neutral
- Entered prospective fault current applies at the installation point
- Preliminary engineering estimate only. Verify the final design against the current applicable standard, local rules, manufacturer data, and project conditions.
- The calculator does not declare that an AFDD is legally required. Confirm the current local wiring rules, adopted edition, exceptions, and project specification.
- AFDD, residual-current, overload, and short-circuit functions must all be verified for the exact ordered model.
- The equations screen ratings only. Whether AFDD protection is required is determined by current local rules and the project risk assessment.
Sources
- IEC 62606, arc-fault detection devicesEdition not stated on this page; clause and table identifiers are preserved verbatim.
Assumptions
- VIOX VAF1-40 and VAF3-40M published envelope: 240 V AC, 1P+N, 6-40 A, B/C, Type A 10/30 mA, 6 kA
- Final circuit supplied line-to-neutral
- Entered prospective fault current applies at the installation point
Important Warnings
- Preliminary engineering estimate only. Verify the final design against the current applicable standard, local rules, manufacturer data, and project conditions.
- The calculator does not declare that an AFDD is legally required. Confirm the current local wiring rules, adopted edition, exceptions, and project specification.
- AFDD, residual-current, overload, and short-circuit functions must all be verified for the exact ordered model.