Buck-Boost Transformer Calculator
Single-phase AC only. Theoretical transformed kVA is not the autotransformer load kVA or necessarily its physical nameplate kVA.
ΔV = |Vout − Vin|I = 1000Sload/VoutSt = ΔV × I/1000Sn = 24I/1000where:
- Vin
- Source voltage[V]
- Vout
- Target load voltage[V]
- ΔV
- Voltage correction[V]
- I
- Load current[A]
- Sload
- Load apparent power[kVA]
- St
- Theoretical transformed capacity[kVA]
- Sn
- 24 V winding nameplate requirement[kVA]
Calculation basis
Calculate single-phase voltage correction, load current and theoretical transformed kVA. Check documented 208/230 V winding-based capacity separately.
Single-phase AC only. Theoretical transformed kVA is not the autotransformer load kVA or necessarily its physical nameplate kVA.
Verified tables and sources
Schneider specifies 24 V times output load current for single-phase 208/230 V selection. The table lists verified nameplate sizes from the Acme 120 × 240 / 12–24 V family; final selection still requires its wiring and capacity chart.
| kVA |
|---|
| 0.05 |
| 0.1 |
| 0.15 |
| 0.25 |
| 0.5 |
| 0.75 |
| 1 |
| 1.5 |
| 2 |
Worked examples
208 V to 230 V at 10 kVA gives ΔV = 22 V, I = 43.48 A and theoretical transformed capacity 0.9565 kVA.
A 24 V winding carrying 43.48 A needs 1.0435 kVA of nameplate capacity. The next size in the documented family is 1.5 kVA.
Method & Sources
Method
Formula used
ΔV = |Vout − Vin|I = 1000Sload/VoutSt = ΔV × I/1000Sn = 24I/1000
Input basis
Single-phase AC only. Theoretical transformed kVA is not the autotransformer load kVA or necessarily its physical nameplate kVA.
- Source voltage [V]
- Target load voltage [V]
- Known load quantity
- Load apparent power [kVA]
- Load current [A]
- Vin — Source voltage [V]
- Vout — Target load voltage [V]
- ΔV — Voltage correction [V]
- I — Load current [A]
- Sload — Load apparent power [kVA]
- St — Theoretical transformed capacity [kVA]
- Sn — 24 V winding nameplate requirement [kVA]
Units
V · kVA · A
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- Single-phase AC only. Theoretical transformed kVA is not the autotransformer load kVA or necessarily its physical nameplate kVA.
- Automatic family sizing is limited to 208/230 V using a documented 24 V winding method. Other voltages require manufacturer tables; no three-phase or neutral creation is calculated.
Sources
- Schneider Electric: 208/230 V buck-boost transformer FAQEstimation basisPublished 24 V winding sizing method used for the 208/230 V example.
- Acme Electric 120 x 240 / 12-24 V buck-boost familyEstimation basisPublished transformer nameplate capacities used by the selection table.
Application limits
Automatic family sizing is limited to 208/230 V using a documented 24 V winding method. Other voltages require manufacturer tables; no three-phase or neutral creation is calculated.
No. A buck-boost unit connected as an autotransformer has electrically connected input and output.
Not necessarily. Actual output depends on winding ratio, connection, input variation and regulation; verify the manufacturer diagram.
Assumptions
- Single-phase AC only. Theoretical transformed kVA is not the autotransformer load kVA or necessarily its physical nameplate kVA.
Important Warnings
- Automatic family sizing is limited to 208/230 V using a documented 24 V winding method. Other voltages require manufacturer tables; no three-phase or neutral creation is calculated.