Generator fuel-consumption equations
Actual output power is multiplied by the specific consumption of the nearest listed load point.
Pout = Prated × load%L/hr = Pout × SFCtruntime = Vtank / (L/hr)Cost/day = L/hr × price × h/daywhere:
- Prated
- Generator rated power[kW]
- SFC
- Selected specific fuel consumption[L/kWh]
- Vtank
- Tank volume[L]
- price
- Fuel price per litre[USD/L]
At 100 kW rated power and 75% load, 75 × 0.31 = 23.3 L/hr and a 200 L tank gives 8.6 hours.
How to estimate generator fuel use
Enter rated kW, actual load factor, fuel type, tank volume, price per litre, and daily operating hours. The calculator selects the nearest load point from the fixed SFC table and converts output power to L/hr and gal/hr.
- Enter rated generator power and load factor.
- Select diesel, gasoline, or propane.
- Enter tank volume, fuel price, and daily hours.
- Compare the estimate with manufacturer curves.
Fixed diesel SFC table
This page uses the four specified diesel load points. Gasoline and propane apply the disclosed 1.35 and 1.40 planning coefficients to those values.
| Load point | Diesel SFC | Gasoline factor | Propane factor |
|---|---|---|---|
| 25% | 0.50 L/kWh | × 1.35 | × 1.40 |
| 50% | 0.37 L/kWh | × 1.35 | × 1.40 |
| 75% | 0.31 L/kWh | × 1.35 | × 1.40 |
| 100% | 0.30 L/kWh | × 1.35 | × 1.40 |
Worked example: 100 kW at 75% load
Output is 100 × 0.75 = 75 kW. At the fixed 0.31 L/kWh diesel SFC, consumption is 75 × 0.31 = 23.3 L/hr, or approximately 6.14 gal/hr. A 200 L tank gives 200 / 23.3 = 8.6 hours.
23.3 L/hr × 8.6 h ≈ 200 L
| Rated power | Load | Output | Diesel use | Tank | Runtime |
|---|---|---|---|---|---|
| 100 kW | 75% | 75 kW | 23.3 L/hr | 200 L | 8.6 h |
Method & Sources
Method
Formula used
Pout = Prated × load%L/hr = Pout × SFCtruntime = Vtank / (L/hr)Cost/day = L/hr × price × h/day
Input basis
Actual output power is multiplied by the specific consumption of the nearest listed load point.
- Generator rated power [kW]
- Actual load factor [%]
- Fuel type
- Tank capacity [L]
- Fuel price [USD/L]
- Operating hours per day [h/day]
- Prated — Generator rated power [kW]
- SFC — Selected specific fuel consumption [L/kWh]
- Vtank — Tank volume [L]
- price — Fuel price per litre [USD/L]
Units
kW · % · L · USD/L · h/day · L/kWh
Display and rounding
- Enter rated kW, actual load factor, fuel type, tank volume, price per litre, and daily operating hours. The calculator selects the nearest load point from the fixed SFC table and converts output power to L/hr and gal/hr.
Scope and limits
- The fixed diesel SFC table is 0.50, 0.37, 0.31, and 0.30 L/kWh at 25%, 50%, 75%, and 100% load.
- Gasoline and propane use disclosed diesel multipliers of 1.35 and 1.40 as planning estimates.
- Fuel price is a flat currency amount per litre; taxes, delivery, maintenance, and demand charges are excluded.
- This is a planning estimate, not a certified generator datasheet. Manufacturer fuel-consumption curves govern final selection.
- Part-load fuel consumption is not linear. The tool uses the nearest fixed load point and does not interpolate.
- At 100 kW rated power and 75% load, 75 × 0.31 = 23.3 L/hr and a 200 L tank gives 8.6 hours.
Sources
- Estimation basis: published page formula, assumptions, and warningsEstimation basisNo separate public standard is cited; the published equation and stated input scope form a planning or screening basis.
Continue the generator planning workflow
Check generator kW and kVA capacity separately, then compare energy cost with other operating scenarios.
Limits of the estimate
Real part-load consumption depends on engine speed, alternator efficiency, fuel density, ambient conditions, maintenance, and transient loading. The manufacturer fuel curve and site test govern final fuel logistics.
Assumptions
- The fixed diesel SFC table is 0.50, 0.37, 0.31, and 0.30 L/kWh at 25%, 50%, 75%, and 100% load.
- Gasoline and propane use disclosed diesel multipliers of 1.35 and 1.40 as planning estimates.
- Fuel price is a flat currency amount per litre; taxes, delivery, maintenance, and demand charges are excluded.
Important Warnings
- This is a planning estimate, not a certified generator datasheet. Manufacturer fuel-consumption curves govern final selection.
- Part-load fuel consumption is not linear. The tool uses the nearest fixed load point and does not interpolate.