Neutral-current equations
The fundamental result uses the stated equal-angle phasor assumption. Third-harmonic phase components are summed in the neutral before combining by root-sum-square.
IF = √(IA² + IB² + IC² − IA×IB − IB×IC − IC×IA)I3N = 0.01 × (hA×IA + hB×IB + hC×IC)IN = √(IF² + I3N²)Utilization = 100 × IN / Iratedwhere:
- IA, IB, IC
- Phase fundamental RMS currents[A]
- IF
- Fundamental neutral-current phasor magnitude[A]
- hA, hB, hC
- Third-harmonic content of each phase[%]
- I3N
- Arithmetic third-harmonic neutral sum[A]
- IN
- Total estimated neutral current[A]
- Irated
- Optional corrected neutral ampacity[A]
For 100/80/60 A with 30% third harmonic on each phase, the fundamental is 34.6 A, the harmonic sum is 72 A, and the total is 79.9 A.
How the neutral-current estimate works
Enter the three fundamental phase currents and, when relevant, each phase's third-harmonic percentage. The fundamental result uses the phasor relationship for equal displacement power-factor angles; the third-harmonic components are added arithmetically.
- Enter one simultaneous current for each phase.
- Enter each third-harmonic percentage, or leave all values at zero.
- Optionally enter corrected neutral ampacity.
- Review fundamental, harmonic, total current and utilization.
Three worked neutral-current cases
The examples separate the fundamental phasor result from the triplen harmonic component. The final value is the root-sum-square of those two components.
| Case | Fundamental | Third harmonic | Total |
|---|---|---|---|
| 100 / 80 / 60 A | 34.6 A | 0 A | 34.6 A |
| 100 / 80 / 60 A; 30% each | 34.6 A | 30 + 24 + 18 = 72 A | 79.9 A |
| 100 / 100 / 100 A; 30% each | 0 A | 30 + 30 + 30 = 90 A | 90.0 A |
Method & Sources
Method
Formula used
IF = √(IA² + IB² + IC² − IA×IB − IB×IC − IC×IA)I3N = 0.01 × (hA×IA + hB×IB + hC×IC)IN = √(IF² + I3N²)Utilization = 100 × IN / Irated
Input basis
The fundamental result uses the stated equal-angle phasor assumption. Third-harmonic phase components are summed in the neutral before combining by root-sum-square.
- Phase A fundamental current [A]
- Phase B fundamental current [A]
- Phase C fundamental current [A]
- Phase A third-harmonic content [%]
- Phase B third-harmonic content [%]
- Phase C third-harmonic content [%]
- Neutral conductor ampacity [A]
- IA, IB, IC — Phase fundamental RMS currents [A]
- IF — Fundamental neutral-current phasor magnitude [A]
- hA, hB, hC — Third-harmonic content of each phase [%]
- I3N — Arithmetic third-harmonic neutral sum [A]
- IN — Total estimated neutral current [A]
- Irated — Optional corrected neutral ampacity [A]
Units
A · %
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- The three phase currents represent one measurement window and have the same displacement power-factor angle.
- Entered third-harmonic percentages are relative to each phase fundamental current and are treated as in-phase triplen components in the neutral.
- The total combines the fundamental phasor result and the arithmetic third-harmonic sum by root-sum-square.
- Different phase angles, other triplen orders, waveform phase data, or measured spectra can require a full harmonic phasor study.
- NEC 220.61 is mentioned only as qualitative context; this calculator does not reproduce its detailed load-sizing provisions or establish code compliance.
- For 100/80/60 A with 30% third harmonic on each phase, the fundamental is 34.6 A, the harmonic sum is 72 A, and the total is 79.9 A.
Sources
- Estimation basis: published page formula, assumptions, and warningsEstimation basisNo separate public standard is cited; the published equation and stated input scope form a planning or screening basis.
Balanced fundamental does not mean zero neutral
Equal fundamental phase currents at 120-degree spacing cancel in the neutral. Third harmonics are separated by three times 120 degrees, or 360 degrees, so they occupy the same phase and add in the neutral.
100 A balanced fundamental → 0 A fundamental neutral
30% third harmonic on each phase → 30 + 30 + 30 = 90 A
Total neutral = 90.0 A
Ampacity and NEC context
The optional ampacity compares total neutral current with the corrected conductor capacity. NEC 220.61 is mentioned only as qualitative context for neutral-load sizing; this page does not restate detailed code provisions or claim compliance.
Current and voltage unbalanceHarmonic and THD analysisThree-phase power
Assumptions
- The three phase currents represent one measurement window and have the same displacement power-factor angle.
- Entered third-harmonic percentages are relative to each phase fundamental current and are treated as in-phase triplen components in the neutral.
- The total combines the fundamental phasor result and the arithmetic third-harmonic sum by root-sum-square.
Important Warnings
- Different phase angles, other triplen orders, waveform phase data, or measured spectra can require a full harmonic phasor study.
- NEC 220.61 is mentioned only as qualitative context; this calculator does not reproduce its detailed load-sizing provisions or establish code compliance.