Motors, Contactors & Drives

Three-Phase Voltage Unbalance Calculator

Calculate three-phase voltage unbalance, voltage-window thresholds, and select a starting VIOX FCP18 monitoring-relay function.

Three-phase voltage unbalance equation

The calculator averages three like-for-like voltage readings and expresses the largest deviation from that average as a percentage.

Average voltage
Vavg = (V1 + V2 + V3) / 3
FCP18-style voltage asymmetry
Va% = (Vmax - Vmin) / Vavg × 100
Maximum-deviation unbalance
Vu% = max(|Vn - Vavg|) / Vavg × 100
Monitoring window
Uhigh = Un(1 + khigh), Ulow = Un(1 - klow)

where:

V1, V2, V3
Three line-to-line or three line-to-neutral readings[V]
Vavg
Arithmetic average of the three readings[V]
Va%
Voltage spread divided by average, used for the FCP18-style asymmetry result[%]
Vu%
Maximum-deviation voltage unbalance shown as a secondary metric[%]
Un
Nominal monitored voltage[V]
khigh, klow
Overvoltage and undervoltage settings as decimals

Use the same measurement basis for all three readings. Equipment limits, relay delays, wiring system, and manufacturer instructions determine the final protection setting.

How to calculate voltage unbalance

Enter three line-to-line readings for a three-wire system or three line-to-neutral readings for a four-wire system. The calculator finds their average, the largest absolute deviation, and the deviation percentage.

  1. Use the same measurement basis for all phases.
  2. Record stable RMS readings.
  3. Calculate average voltage.
  4. Find maximum deviation.
  5. Compare with equipment and relay limits.

Voltage asymmetry example

Readings of 400 V, 392 V, and 408 V average 400 V. The FCP18-style range-to-average asymmetry is 4%, while the secondary maximum-deviation method gives 2%. The page labels both results so they are not treated as interchangeable.

Va = (408 - 392) / 400 × 100 = 4%

Vu = 8 / 400 × 100 = 2%

Why small voltage differences matter

Three-phase motors can develop a much larger current imbalance than the measured voltage imbalance, increasing negative-sequence heating, vibration, torque pulsation, and insulation stress. Use the motor manufacturer's limit rather than assuming one percentage suits every load.

Choosing an FCP18 function

Choose FCP18-01 for phase loss and sequence, FCP18-02 for a voltage window, FCP18-03 for comprehensive monitoring with adjustable delay, FCP18-04 for adjustable asymmetry, FCP18-05 for imbalance-focused protection, or FCP18-06 for fixed OEM settings. Verify voltage and wiring variants before ordering.

Assumptions

  • The three entered values use the same measurement basis
  • The percentage is a maximum-deviation-from-average calculation
  • FCP18 selection follows the function comparison described in the VIOX product guide

Important Warnings

  • Do not mix line-to-line and line-to-neutral readings in one calculation.
  • Acceptable voltage unbalance depends on the motor or equipment manufacturer; even modest voltage unbalance can produce much larger current unbalance.

FAQ

How is voltage asymmetry calculated?

For the FCP18 selection result, subtract the minimum reading from the maximum reading, divide by the three-reading average, and multiply by 100. The page also shows the maximum-deviation method as a separate metric.

What is the difference between FCP18-03 and FCP18-04?

FCP18-03 provides full monitoring with adjustable delay and fixed 8% asymmetry. FCP18-04 provides full monitoring with adjustable 5-15% asymmetry and fixed delay.

Does the relay replace overload or surge protection?

No. It supervises sustained supply-voltage conditions. Motor overload protection and transient surge protection are separate functions.