Motor Starting Current Calculator (Locked Rotor Amps)

Estimate motor locked-rotor amps from a nameplate NEC Code letter, or apply an editable starting-current multiplier to motor full-load amps.

NEC 430.7(B)

Motor locked-rotor current equations

The nameplate Code letter provides a kVA/HP interval. Multiplier mode instead scales full-load current by the selected starting factor.

Code-letter starting kVA
Sstart = (kVA/HP) × HP
Three-phase LRA
ILRA = 1000 × Sstart / (√3 × VLL)
Single-phase LRA
ILRA = 1000 × Sstart / V
Multiplier mode
Istart = kstart × IFLA

where:

Sstart
Locked-rotor apparent power estimate[kVA]
kVA/HP
NEC Code-letter interval or midpoint[kVA/HP]
HP
Motor rated horsepower[HP]
VLL
Three-phase line-to-line voltage[V]
ILRA
Estimated locked-rotor current[A]
kstart
Selected starting-current multiplier

For Code G at 20 HP and 460 V three-phase, the midpoint gives about 119 kVA and 149 A; the code bounds give about 141–158 A.

How to find motor starting current

A motor nameplate Code letter groups locked-rotor kilovolt-amperes per horsepower. Select the letter printed on the motor, enter rated HP and voltage, and choose single-phase or three-phase. The calculator converts the code interval to starting kVA and locked-rotor amperes.

  1. Find the motor Code letter on the nameplate.
  2. Enter motor HP, rated voltage and phase.
  3. Read starting kVA, midpoint LRA and the lower-to-upper LRA range.
  4. Use multiplier mode when an editable FLA-based starting factor better matches the project.

Code G worked example

For a 20 HP, 460 V three-phase motor with Code G, NEC Table 430.7(B) spans 5.60 to 6.29 kVA/HP. The arithmetic midpoint is 5.945, displayed as 5.95 kVA/HP.

Sstart = 5.945 × 20 = 118.9 kVA ≈ 119 kVA

LRA(mid) = 119000 ÷ (√3 × 460) ≈ 149 A

LRA range ≈ 141–158 A

Input or resultValue
HP20 HP
Voltage460 V
PhaseThree-phase
CodeG
kVA/HP5.60–6.29 (mid 5.945)
Starting kVA119 kVA
LRA149 A
LRA interval141–158 A

Method & Sources

Method

Formula used

  • Sstart = (kVA/HP) × HP
  • ILRA = 1000 × Sstart / (√3 × VLL)
  • ILRA = 1000 × Sstart / V
  • Istart = kstart × IFLA

Input basis

The nameplate Code letter provides a kVA/HP interval. Multiplier mode instead scales full-load current by the selected starting factor.

  • Input method
  • Motor rated power [HP]
  • Motor rated voltage [V]
  • Supply phase
  • NEC Code letter from nameplate
  • Motor full-load current [A]
  • Starting method preset
  • Custom starting-current multiplier [× FLA]
  • Sstart — Locked-rotor apparent power estimate [kVA]
  • kVA/HP — NEC Code-letter interval or midpoint [kVA/HP]
  • HP — Motor rated horsepower [HP]
  • VLL — Three-phase line-to-line voltage [V]
  • ILRA — Estimated locked-rotor current [A]
  • kstart — Selected starting-current multiplier

Units

HP · V · A · × FLA · kVA · kVA/HP

Display and rounding

No separate display or rounding rule is stated on this page.

Scope and limits

  • The motor nameplate code letter brackets locked-rotor kVA per horsepower; the midpoint is an estimate, not a guarantee for one motor.
  • Code-letter current is calculated at the entered rated voltage and phase using the standard kVA/HP interval.
  • Multiplier mode applies a user-selected starting-current factor to full-load current and does not represent a complete motor-starting study.
  • Verify the actual motor nameplate, connection, starter setting, protection curve, and controller rating before selecting equipment.
  • Starting current alone does not establish voltage-dip, thermal, contactor AC-3, breaker magnetic, or generator transient compliance.
  • For Code G at 20 HP and 460 V three-phase, the midpoint gives about 119 kVA and 149 A; the code bounds give about 141–158 A.

Sources

  • NFPA 70, National Electrical Code (NEC), Table 430.7(B)Edition not stated on this page; clause and table identifiers are preserved verbatim.

NEC Table 430.7(B): code letters A–V

Source: NFPA 70, NEC Table 430.7(B), locked-rotor kilovolt-amperes per horsepower. Code V is open-ended and therefore has no finite upper bound.

Code letterMinimum kVA/HPMaximum kVA/HP
A0.003.14
B3.153.54
C3.553.99
D4.004.49
E4.504.99
F5.005.59
G5.606.29
H6.307.09
J7.107.99
K8.008.99
L9.009.99
M10.0011.19
N11.2012.49
P12.5013.99
R14.0015.99
S16.0017.99
T18.0019.99
U20.0022.39
V22.40No finite upper limit

Starting-current checks

Use the result as an input to voltage-dip, breaker magnetic-pickup, contactor duty, and generator transient checks. Related calculators provide those separate screens without treating LRA alone as a complete design.

Assumptions

  • The motor nameplate code letter brackets locked-rotor kVA per horsepower; the midpoint is an estimate, not a guarantee for one motor.
  • Code-letter current is calculated at the entered rated voltage and phase using the standard kVA/HP interval.
  • Multiplier mode applies a user-selected starting-current factor to full-load current and does not represent a complete motor-starting study.

Important Warnings

  • Verify the actual motor nameplate, connection, starter setting, protection curve, and controller rating before selecting equipment.
  • Starting current alone does not establish voltage-dip, thermal, contactor AC-3, breaker magnetic, or generator transient compliance.

FAQ

What does the motor Code letter mean?

NEC Table 430.7(B) maps each nameplate code letter to a locked-rotor kVA per horsepower interval. The tool uses the interval to estimate starting kVA and LRA.

Why does the result show a range as well as a midpoint?

The code letter gives a range for a population of motors. The midpoint is a central screening value, while the lower and upper bounds show the uncertainty within that code.

Why is Code V reported differently?

Code V starts at 22.40 kVA/HP and has no finite upper limit, so a midpoint or upper current would require inventing an endpoint. The tool reports the lower bound only.

When should I use multiplier mode?

Use it for an early screen when measured or manufacturer starting current is better represented as a multiple of FLA. Replace the preset with verified project data when available.

Does this replace a motor-starting voltage-dip study?

No. The result supplies an LRA or multiplier estimate. A complete study also needs source impedance, transformer and cable data, motor acceleration, protection behavior, and running load.