Motor locked-rotor current equations
The nameplate Code letter provides a kVA/HP interval. Multiplier mode instead scales full-load current by the selected starting factor.
Sstart = (kVA/HP) × HPILRA = 1000 × Sstart / (√3 × VLL)ILRA = 1000 × Sstart / VIstart = kstart × IFLAwhere:
- Sstart
- Locked-rotor apparent power estimate[kVA]
- kVA/HP
- NEC Code-letter interval or midpoint[kVA/HP]
- HP
- Motor rated horsepower[HP]
- VLL
- Three-phase line-to-line voltage[V]
- ILRA
- Estimated locked-rotor current[A]
- kstart
- Selected starting-current multiplier
For Code G at 20 HP and 460 V three-phase, the midpoint gives about 119 kVA and 149 A; the code bounds give about 141–158 A.
How to find motor starting current
A motor nameplate Code letter groups locked-rotor kilovolt-amperes per horsepower. Select the letter printed on the motor, enter rated HP and voltage, and choose single-phase or three-phase. The calculator converts the code interval to starting kVA and locked-rotor amperes.
- Find the motor Code letter on the nameplate.
- Enter motor HP, rated voltage and phase.
- Read starting kVA, midpoint LRA and the lower-to-upper LRA range.
- Use multiplier mode when an editable FLA-based starting factor better matches the project.
Code G worked example
For a 20 HP, 460 V three-phase motor with Code G, NEC Table 430.7(B) spans 5.60 to 6.29 kVA/HP. The arithmetic midpoint is 5.945, displayed as 5.95 kVA/HP.
Sstart = 5.945 × 20 = 118.9 kVA ≈ 119 kVA
LRA(mid) = 119000 ÷ (√3 × 460) ≈ 149 A
LRA range ≈ 141–158 A
| Input or result | Value |
|---|---|
| HP | 20 HP |
| Voltage | 460 V |
| Phase | Three-phase |
| Code | G |
| kVA/HP | 5.60–6.29 (mid 5.945) |
| Starting kVA | 119 kVA |
| LRA | 149 A |
| LRA interval | 141–158 A |
Method & Sources
Method
Formula used
Sstart = (kVA/HP) × HPILRA = 1000 × Sstart / (√3 × VLL)ILRA = 1000 × Sstart / VIstart = kstart × IFLA
Input basis
The nameplate Code letter provides a kVA/HP interval. Multiplier mode instead scales full-load current by the selected starting factor.
- Input method
- Motor rated power [HP]
- Motor rated voltage [V]
- Supply phase
- NEC Code letter from nameplate
- Motor full-load current [A]
- Starting method preset
- Custom starting-current multiplier [× FLA]
- Sstart — Locked-rotor apparent power estimate [kVA]
- kVA/HP — NEC Code-letter interval or midpoint [kVA/HP]
- HP — Motor rated horsepower [HP]
- VLL — Three-phase line-to-line voltage [V]
- ILRA — Estimated locked-rotor current [A]
- kstart — Selected starting-current multiplier
Units
HP · V · A · × FLA · kVA · kVA/HP
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- The motor nameplate code letter brackets locked-rotor kVA per horsepower; the midpoint is an estimate, not a guarantee for one motor.
- Code-letter current is calculated at the entered rated voltage and phase using the standard kVA/HP interval.
- Multiplier mode applies a user-selected starting-current factor to full-load current and does not represent a complete motor-starting study.
- Verify the actual motor nameplate, connection, starter setting, protection curve, and controller rating before selecting equipment.
- Starting current alone does not establish voltage-dip, thermal, contactor AC-3, breaker magnetic, or generator transient compliance.
- For Code G at 20 HP and 460 V three-phase, the midpoint gives about 119 kVA and 149 A; the code bounds give about 141–158 A.
Sources
- NFPA 70, National Electrical Code (NEC), Table 430.7(B)Edition not stated on this page; clause and table identifiers are preserved verbatim.
NEC Table 430.7(B): code letters A–V
Source: NFPA 70, NEC Table 430.7(B), locked-rotor kilovolt-amperes per horsepower. Code V is open-ended and therefore has no finite upper bound.
| Code letter | Minimum kVA/HP | Maximum kVA/HP |
|---|---|---|
| A | 0.00 | 3.14 |
| B | 3.15 | 3.54 |
| C | 3.55 | 3.99 |
| D | 4.00 | 4.49 |
| E | 4.50 | 4.99 |
| F | 5.00 | 5.59 |
| G | 5.60 | 6.29 |
| H | 6.30 | 7.09 |
| J | 7.10 | 7.99 |
| K | 8.00 | 8.99 |
| L | 9.00 | 9.99 |
| M | 10.00 | 11.19 |
| N | 11.20 | 12.49 |
| P | 12.50 | 13.99 |
| R | 14.00 | 15.99 |
| S | 16.00 | 17.99 |
| T | 18.00 | 19.99 |
| U | 20.00 | 22.39 |
| V | 22.40 | No finite upper limit |
Starting-current checks
Use the result as an input to voltage-dip, breaker magnetic-pickup, contactor duty, and generator transient checks. Related calculators provide those separate screens without treating LRA alone as a complete design.
Motor starting voltage dropMCB inrush compatibilityMotor full-load currentGenerator sizing
Assumptions
- The motor nameplate code letter brackets locked-rotor kVA per horsepower; the midpoint is an estimate, not a guarantee for one motor.
- Code-letter current is calculated at the entered rated voltage and phase using the standard kVA/HP interval.
- Multiplier mode applies a user-selected starting-current factor to full-load current and does not represent a complete motor-starting study.
Important Warnings
- Verify the actual motor nameplate, connection, starter setting, protection curve, and controller rating before selecting equipment.
- Starting current alone does not establish voltage-dip, thermal, contactor AC-3, breaker magnetic, or generator transient compliance.