Motor Speed & Slip Calculator

Calculate induction-motor synchronous speed, slip, rotor speed and rotor frequency from poles, supply frequency and measured speed or known slip.

IEC 60034-1NEMA MG 1

Induction motor speed and slip equations

Use the pole count and supply frequency to find synchronous speed, then use measured rotor speed or known slip for the remaining quantities. The symbol s is a decimal fraction; s% is its percentage display.

Synchronous speed
ns = 120 × f / P
Slip from measured speed
s = (ns − nr) / ns
Displayed slip percentage
s% = 100s
Rotor speed from slip
nr = ns × (1 − s)
Rotor frequency
fr = s × f

where:

ns
Synchronous speed[rpm]
nr
Rotor speed[rpm]
P
Even pole count from 2 to 12
f
Supply frequency[Hz]
s
Slip as a decimal fraction
s%
Slip displayed as a percentage[%]
fr
Rotor frequency[Hz]

Only even pole counts 2, 4, 6, 8, 10 and 12 are accepted. nr > ns is the generating region and stops the calculation; nr = 0 and nr = ns are the 100% and 0% slip boundaries. No typical full-load slip range is asserted.

How to calculate motor speed and slip

Select measured rotor speed or known slip, enter the even pole count and the supply frequency, and review synchronous speed, slip, rotor speed and rotor frequency. A 3% slip input is converted to s = 0.03 before it enters the equations.

  1. Choose measured rotor speed or known slip.
  2. Select an even pole count from 2 to 12.
  3. Enter the supply frequency in Hz.
  4. Compare the result with nameplate speed and actual load conditions.

Worked examples

Example 1: 4 poles, 60 Hz and 1760 rpm give ns = 120 × 60 / 4 = 1800 rpm, s% = (1800 − 1760) / 1800 × 100 = 2.22% and fr = 0.0222 × 60 = 1.33 Hz. Example 2: 4 poles, 50 Hz and 3% slip give ns = 1500 rpm, s = 0.03 and nr = 1500 × (1 − 0.03) = 1455 rpm. Example 3: nr = ns gives 0% slip and nr = 0 gives 100% slip.

1800 rpm · 2.22% · 1.33 Hz

1500 rpm · 3% · 1455 rpm

nr = ns → 0% · nr = 0 → 100%

CasePoles / fInputnsSlipnr / fr
14 / 60 Hz1760 rpm1800 rpm2.22%1760 rpm / 1.33 Hz
24 / 50 Hz3%1500 rpm3%1455 rpm / 1.50 Hz
3a4 / 50 Hznr = 1500 rpm1500 rpm0%1500 rpm / 0 Hz
3b4 / 50 Hznr = 0 rpm1500 rpm100%0 rpm / 50 Hz

Method & Sources

Method

Formula used

  • ns = 120 × f / P
  • s = (ns − nr) / ns
  • s% = 100s
  • nr = ns × (1 − s)
  • fr = s × f

Input basis

Use the pole count and supply frequency to find synchronous speed, then use measured rotor speed or known slip for the remaining quantities. The symbol s is a decimal fraction; s% is its percentage display.

  • Calculation mode
  • Number of poles (P)
  • Supply frequency (f) [Hz]
  • Measured rotor speed (nr) [rpm]
  • Known slip (s%) [%]
  • ns — Synchronous speed [rpm]
  • nr — Rotor speed [rpm]
  • P — Even pole count from 2 to 12
  • f — Supply frequency [Hz]
  • s — Slip as a decimal fraction
  • s% — Slip displayed as a percentage [%]
  • fr — Rotor frequency [Hz]

Units

Hz · rpm · %

Display and rounding

No separate display or rounding rule is stated on this page.

Scope and limits

  • The motor is a fixed-frequency induction machine operating in the motoring region.
  • P is an even pole count from 2 to 12; f is the measured or nameplate supply frequency.
  • s is a decimal fraction in the equations; the page displays s% = 100s as a percentage.
  • The 0% and 100% slip boundaries represent ideal no-load and locked-rotor conditions.
  • If nr > ns, slip is negative and the machine is in the generating region; this page stops without returning a result.
  • Real shaft speed also depends on load, voltage, temperature, rotor design, VFD control and measurement tolerance.
  • Only even pole counts 2, 4, 6, 8, 10 and 12 are accepted. nr > ns is the generating region and stops the calculation; nr = 0 and nr = ns are the 100% and 0% slip boundaries. No typical full-load slip range is asserted.

Sources

  • IEC 60034-1, rotating electrical machines: slip definitionEdition not stated on this page; clause and table identifiers are preserved verbatim.
  • NEMA MG 1, motors and generators: rated-slip referenceEdition not stated on this page; clause and table identifiers are preserved verbatim.
  • IEC 60034-1, Rotating Electrical Machines, Part 1: Rating and PerformanceSlip-definition reference for induction motors; the page states formulas and input scope without asserting a typical full-load slip range.
  • NEMA MG 1, Motors and GeneratorsRated-slip reference cited on this page; no typical full-load slip range is asserted without verbatim verification of the standard text.

Continue the motor-control workflow

Use the linked calculators for shaft torque, full-load current and locked-rotor starting current. These are separate checks and do not replace motor nameplate or manufacturer data.

Scope and source basis

IEC 60034-1 provides the slip definition used here, while NEMA MG 1 is the cited rated-slip reference. No typical full-load slip range is stated because that numeric range has not been verified word-for-word from NEMA MG 1 on this page.

Assumptions

  • The motor is a fixed-frequency induction machine operating in the motoring region.
  • P is an even pole count from 2 to 12; f is the measured or nameplate supply frequency.
  • s is a decimal fraction in the equations; the page displays s% = 100s as a percentage.
  • The 0% and 100% slip boundaries represent ideal no-load and locked-rotor conditions.

Important Warnings

  • If nr > ns, slip is negative and the machine is in the generating region; this page stops without returning a result.
  • Real shaft speed also depends on load, voltage, temperature, rotor design, VFD control and measurement tolerance.

FAQ

What does a 4-pole motor run at on 60 Hz?

ns = 120 × 60 / 4 = 1800 rpm. A nameplate rotor speed of 1760 rpm gives s% = (1800 − 1760) / 1800 × 100 = 2.22%.

Is slip entered as 3 or 0.03?

Enter the displayed percentage, 3%. The equations use the decimal fraction s = 0.03 and show the result as s% = 3%.

Why does the calculator reject a rotor speed above synchronous speed?

That produces negative slip and indicates the generating region. This calculator covers only the motoring region and stops without a numeric result.

What are the two slip boundaries?

nr = ns gives s% = 0%, the ideal no-load boundary; nr = 0 gives s% = 100%, the locked-rotor boundary.

What does rotor frequency mean?

fr = s × f uses slip as a decimal fraction. At 60 Hz and 2.22% slip, fr is approximately 1.33 Hz.