Transformer kVA to Amps Full-Load Chart
kVA to amps equation
This page isolates the kVA to amps relationship so the phase, power-factor, efficiency, or time basis is visible.
I = 1000 × kVA / (kφ × V)where:
- I
- Current[A]
- kVA
- Apparent power[kVA]
- V
- Voltage[V]
- kφ
- Phase factor: 1 for DC or single-phase and √3 for balanced three-phase line-to-line voltage
Use consistent units and check whether the input power is electrical input or shaft output.
How to convert kVA to amps
Convert kVA to amps with the correct phase, power-factor, efficiency, time, or voltage basis where the selected conversion requires it.
- Identify the quantities you already know.
- Select the applicable phase, power factor, efficiency, or time basis.
- Enter nominal values and compare the result with the equipment nameplate.
Worked example
kVA to amps: 25 kVA, 400 V, three-phase AC gives 36.1 A.
kVA → amps = 36.1 A
Method & Sources
Method
Formula used
I = 1000 × kVA / (kφ × V)
Input basis
This page isolates the kVA to amps relationship so the phase, power-factor, efficiency, or time basis is visible.
- Apparent power [kVA]
- Voltage [V]
- System
- I — Current [A]
- kVA — Apparent power [kVA]
- V — Voltage [V]
- kφ — Phase factor: 1 for DC or single-phase and √3 for balanced three-phase line-to-line voltage
Units
kVA · V · A
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- Nominal values are used for the entered voltage, phase, power factor, efficiency, or time.
- Balanced phases and nominal voltage are assumed; verify the actual connection and nameplate values for final engineering use.
- This is a conversion aid, not a complete equipment selection or protection study.
- Use consistent units and check whether the input power is electrical input or shaft output.
Sources
- NIST Special Publication 811SI units and defined conversion relationships used by the focused conversion pages.
- VIOX low-voltage electrical formulas guidePublished formula reference linked from this page.
Common kVA to amps values
The table changes only the first input while retaining the page's documented example assumptions.
| Input kVA | Result amps |
|---|---|
| 5 kVA | 7.217 A |
| 15.0 kVA | 21.7 A |
| 30.0 kVA | 43.3 A |
Assumptions and limits
Balanced phases and nominal voltage are assumed; verify the actual connection and nameplate values for final engineering use.
Formulas and sources
The equations use the SI relationships for electrical power, energy, charge, and the defined mechanical horsepower value. Verify local code, equipment data, and project assumptions before engineering use.
NIST SI unit rules and style guideVIOX electrical formulas reference
Assumptions
- Nominal values are used for the entered voltage, phase, power factor, efficiency, or time.
- Balanced phases and nominal voltage are assumed; verify the actual connection and nameplate values for final engineering use.
Important Warnings
- This is a conversion aid, not a complete equipment selection or protection study.