UPS sizing and runtime equations
The VA and W ratings use the same reserve margin, while runtime is based on actual load and available AC energy.
VA = W / PFVArec = VA × (1 + margin)Wrec = W × (1 + margin)tmin = 60 × Wh × η / Wwhere:
- W
- Actual protected load[W]
- PF
- UPS output power factor
- margin
- Reserve margin as a decimal
- Wh
- Battery energy[Wh]
- η
- Inverter efficiency as a decimal
- tmin
- Estimated backup time[min]
For 500 W at PF 0.9, the planning result is 694 VA and 625 W; 1,000 Wh at 90% efficiency gives 108 minutes.
How to size a UPS
Enter real load watts and the UPS output power factor first. Add a reserve margin to both VA and W ratings, then enter battery energy and inverter efficiency for the runtime estimate.
- Enter the protected load in W.
- Enter output PF and reserve margin.
- Enter battery Wh and inverter efficiency.
- Verify both VA and W ratings with the manufacturer.
Worked example: 500 W UPS
A 500 W load at PF 0.9 needs 500 / 0.9 = 556 VA. A 25% reserve gives rounded planning values of 694 VA and 625 W. With 1,000 Wh of battery energy and 90% inverter efficiency, backup time is 1,000 × 0.90 / 500 × 60 = 108 minutes.
556 VA → 694 VA with 25% reserve
| Quantity | Input | Result |
|---|---|---|
| 500 W | PF 0.9 | 556 VA |
| Reserve | 25% | 694 VA / 625 W |
| Battery | 1,000 Wh · 90% | 108 min |
Method & Sources
Method
Formula used
VA = W / PFVArec = VA × (1 + margin)Wrec = W × (1 + margin)tmin = 60 × Wh × η / W
Input basis
The VA and W ratings use the same reserve margin, while runtime is based on actual load and available AC energy.
- Total protected load [W]
- UPS output power factor
- Reserve margin [%]
- Battery energy [Wh]
- Inverter efficiency [%]
- W — Actual protected load [W]
- PF — UPS output power factor
- margin — Reserve margin as a decimal
- Wh — Battery energy [Wh]
- η — Inverter efficiency as a decimal
- tmin — Estimated backup time [min]
Units
W · % · Wh · min
Display and rounding
- A 500 W load at PF 0.9 needs 500 / 0.9 = 556 VA. A 25% reserve gives rounded planning values of 694 VA and 625 W. With 1,000 Wh of battery energy and 90% inverter efficiency, backup time is 1,000 × 0.90 / 500 × 60 = 108 minutes.
Scope and limits
- The protected load is constant and expressed as real input watts.
- Battery Wh is usable nameplate energy before the entered inverter efficiency adjustment.
- Rounded VA and W planning values do not represent a specific commercial UPS family.
- A UPS must satisfy both its VA and W ratings, plus crest factor, load steps, bypass, and temperature limits.
- Use manufacturer constant-power discharge data for guaranteed runtime; battery aging and high discharge rates reduce autonomy.
- For 500 W at PF 0.9, the planning result is 694 VA and 625 W; 1,000 Wh at 90% efficiency gives 108 minutes.
Sources
- Estimation basis: published page formula, assumptions, and warningsEstimation basisNo separate public standard is cited; the published equation and stated input scope form a planning or screening basis.
VA, watts, and runtime are different checks
The VA rating limits apparent output current, while the W rating limits real output power. The battery Wh and efficiency determine how long the actual load can run. Increasing the reserve margin does not make the battery last longer.
Continue the backup-power workflow
Use the linked calculators to check detailed battery bank configuration, discharge rate, and inverter continuous and surge ratings.
Assumptions
- The protected load is constant and expressed as real input watts.
- Battery Wh is usable nameplate energy before the entered inverter efficiency adjustment.
- Rounded VA and W planning values do not represent a specific commercial UPS family.
Important Warnings
- A UPS must satisfy both its VA and W ratings, plus crest factor, load steps, bypass, and temperature limits.
- Use manufacturer constant-power discharge data for guaranteed runtime; battery aging and high discharge rates reduce autonomy.