HP to amps equation

This page isolates the HP to amps relationship so the phase, power-factor, efficiency, or time basis is visible.

Conversion relation
I = 745.699872 × HP / (kφ × V × PF × η)

where:

I
Current[A]
HP
Mechanical output power[HP]
V
Voltage[V]
PF
Power factor
η
Motor efficiency as a decimal
kφ
Phase factor: 1 for DC or single-phase and √3 for balanced three-phase line-to-line voltage

Use consistent units and check whether the input power is electrical input or shaft output.

How to convert HP to amps

Convert HP to amps with the correct phase, power-factor, efficiency, time, or voltage basis where the selected conversion requires it.

  1. Identify the quantities you already know.
  2. Select the applicable phase, power factor, efficiency, or time basis.
  3. Enter nominal values and compare the result with the equipment nameplate.

Worked example

HP to amps: 15 HP, 400 V, three-phase AC, 0.86, 91 % gives 20.6 A.

HP → amps = 20.6 A

Method & Sources

Method

Formula used

  • I = 745.699872 × HP / (kφ × V × PF × η)

Input basis

This page isolates the HP to amps relationship so the phase, power-factor, efficiency, or time basis is visible.

  • Motor output [HP]
  • Voltage [V]
  • System
  • Power factor
  • Efficiency [%]
  • I — Current [A]
  • HP — Mechanical output power [HP]
  • V — Voltage [V]
  • PF — Power factor
  • η — Motor efficiency as a decimal
  • kφ — Phase factor: 1 for DC or single-phase and √3 for balanced three-phase line-to-line voltage

Units

HP · V · % · A

Display and rounding

No separate display or rounding rule is stated on this page.

Scope and limits

  • Nominal values are used for the entered voltage, phase, power factor, efficiency, or time.
  • Balanced phases and nominal voltage are assumed; verify the actual connection and nameplate values for final engineering use.
  • This is a conversion aid, not a complete equipment selection or protection study.
  • Use consistent units and check whether the input power is electrical input or shaft output.

Sources

Common HP to amps values

The table changes only the first input while retaining the page's documented example assumptions.

Input HPResult amps
1 HP1.375 A
5 HP6.877 A
20.0 HP27.5 A

Assumptions and limits

Balanced phases and nominal voltage are assumed; verify the actual connection and nameplate values for final engineering use.

Formulas and sources

The equations use the SI relationships for electrical power, energy, charge, and the defined mechanical horsepower value. Verify local code, equipment data, and project assumptions before engineering use.

Assumptions

  • Nominal values are used for the entered voltage, phase, power factor, efficiency, or time.
  • Balanced phases and nominal voltage are assumed; verify the actual connection and nameplate values for final engineering use.

Important Warnings

  • This is a conversion aid, not a complete equipment selection or protection study.

FAQ

What formula converts HP to amps?

I = 745.699872 × HP / (kφ × V × PF × η)

Does HP to amps require a power factor?

Yes for AC power calculations. Use the load power factor; enter 1 only for DC or a purely resistive load.

How does phase affect HP to amps?

Three-phase AC uses a √3 factor for line-to-line voltage; single-phase and DC use 1.

Can this HP to amps calculator replace equipment data?

No. Treat the output as a conversion or screening value and verify the actual nameplate, connection, and applicable standard.

Why can amps differ from another calculator?

Different phase conventions, assumed power factor, efficiency, rounding, or whether power is input or output can change the result.