Power-factor equation
Active power, reactive power, and apparent power form a right triangle.
PF = P / Sφ = arccos(PF)Q = √(S² − P²)where:
- P
- Real power[kW]
- S
- Apparent power[kVA]
- Q
- Reactive power[kVAR]
How to calculate power factor
Power factor is real power divided by apparent power. Apparent power combines real and reactive components in a right triangle.
Worked power-factor example
10 kW and 12.5 kVA give PF = 0.80, phase angle 36.87°, and Q = 7.5 kVAR.
Method & Sources
Method
Formula used
PF = P / Sφ = arccos(PF)Q = √(S² − P²)
Input basis
Active power, reactive power, and apparent power form a right triangle.
- Known values
- Real power [kW]
- Apparent power [kVA]
- Reactive power [kVAR]
- System
- Line voltage [V]
- Line current [A]
- P — Real power [kW]
- S — Apparent power [kVA]
- Q — Reactive power [kVAR]
Units
kW · kVA · kVAR · V · A
Display and rounding
No separate display or rounding rule is stated on this page.
Scope and limits
- Balanced AC system for voltage-and-current mode
- Steady-state sinusoidal quantities
- The result describes the entered operating point; harmonics, distortion power, and changing load require waveform or interval analysis.
Sources
- Estimation basis: published page formula, assumptions, and warningsEstimation basisNo separate public standard is cited; the published equation and stated input scope form a planning or screening basis.
Diagnosis versus correction
This page calculates the existing PF from known values. The correction calculator sizes a capacitor bank for a target PF.
Limits of a steady-state result
Harmonics and distorted waveforms can make fundamental-frequency PF differ from true power factor. Use metered interval data for final assessment.
Power-triangle reference
The equations apply the standard sinusoidal steady-state definitions PF = P/S, S² = P² + Q², and φ = arccos(PF). Values are unit conversions of kW, kVA, and kVAR and do not include harmonic distortion power.
Assumptions
- Balanced AC system for voltage-and-current mode
- Steady-state sinusoidal quantities
Important Warnings
- The result describes the entered operating point; harmonics, distortion power, and changing load require waveform or interval analysis.